Setting The Air Adjustment Plate; Burner Set-Up Chart - Riello 40 F10 Installation & Operating Manual

Single stage operation oil burner with manual air shutter
Table of Contents

Advertisement

SETTING THE AIR ADJUSTMENT PLATE

A) Regulation of the combustion air flow is made by adjustment of the manual AIR
ADJUSTMENT PLATE (1) after loosening the FIXING SCREWS (2 & 3). The initial
setting of the air adjustment plate should be made according to Column 5 in the

Burner Set-up Chart.

B) The proper number on the manual AIR
ADJUSTMENT PLATE (1) should line up
with the SETTING INDICATOR (4) on the
fan housing cover. Once set, the air ad-
justment plate should be secured in place
by tightening SCREWS 2 and 3.
C) The final position of the air adjustment
plate will vary on each installation. Use in-
struments to establish the proper settings
for maximum CO
2
zero.
NOTE:
Variations in flue gas, smoke,
CO
and temperature readings may be
2
experienced when the burner cover is put
in place. Therefore, the burner cover
must be in place when making the final
combustion
instrument
ensure proper test results.
1
ACTUAL FIRING
RATE ± 5%
GPH
kg/h
1.45
4.7
1.80
5.8
2.10
6.8
2.40
7.8
2.75
8.9
2.95
9.5
NOZZLES: Monarch R-PLP, Delavan W-B, Danfoss S-B, Steinen SS-S, Hago P.
NOTE: A 60° degree nozzle is suggested, however, a 80° degree nozzle may be
used in cases where the flame is unstable at light-off when operated at low ambient
temperatures.
and a smoke reading of
readings,
BURNER SET-UP CHART
2
NOZZLE
SIZE
GPH
1.25 x 60°
1.50 x 60°
1.75 x 60°
2.00 x 60°
2.25 x 60°
2.50 x 60°
4
to
3
PUMP
TURBULATOR
PRESSURE
PSI
BAR
145
10
145
10
145
10
145
10
150
10.4
140
9.8
F10 - 12
3
4
AIR DAMPER
SETTING
SETTING
1.5
2.0
2.5
3.5
4.0
4.5
2
1
D5231
5
2.7
2.8
3.1
3.4
4.2
4.2