Ps D75 - ABB PS D75 840 Series Installation And Maintenance Instruction

Table of Contents

Advertisement

4.1
PS D75.. 840 without built-in electronic overload protection
LED's
F1: (red)
Fault signal for Phase loss, Thyristor fault, High current switch off.
F2: (red)
Fault signal for Over temperature, Fault on circuit board, Thyristor fault
On: (green) Supply voltage. Illuminates when softstarter has control power.
R: (yellow)
Motor is running. Illuminates when the motor is energised from the softstarter.
T: (yellow)
Top of ramp. Start ramp is finished and stop ramp hasn't begun.
P: (yellow)
Energy saving is active
Fault codes
F1
Phase loss, High current switch off.
F2
Over temperature, Fault on circuit board,
F1 + F2
Thyristor fault (short circuit or open circuit)
Relay Signals
Run / K4
Motor is running. The motor is energised from the softstarter
TOR / K5
Top of ramp. Start ramp is finished and stop ramp hasn't begun. Can be used as a by-
pass signal.
Fault / K6
Phase loss, Thyristor fault, Over temperature, High current switch off, Fault on circuit
board,
Input
Start/Stop
Start when closed, stop when open, 24V, 20mA optocoupler differential input. +24V
and 0V can be supplied from the board if no external supply is used.
Run relay / K4
TOP relay / K5
U
START
60 sec.
STOP
- 15 -
time
<500 ms