Transceiver and Cable Specifications
Component
Power Supply module
– 1100-W AC port-side exhaust
(blue) (NXA-PAC-1100W-PE2)
– 1100-W AC port-side intake
(burgundy)
(NXA-PAC-1100W-PI2)
– 1100-W HVAC/HVDC port-side
exhaust (blue)
(NXA-PUV-1100W-PE)
– 1100-W HVAC/HVDC port-side
intake (burgundy)
(NXA-PUV-1100W-PI)
– 1100-W DC port-side exhaust
(blue) (NXA-PDC-1100W-PE)
– 1100-W DC port-side intake
(burgundy) (NXA-PDC-1100W-PI)
Transceiver and Cable Specifications
To determine which transceivers, adapters, and cables are supported by this switch, see
c/en/us/support/interfaces-modules/transceiver-modules/products-device-support-tables-list.html.
To see the transceiver specifications and installation information, see
interfaces-modules/transceiver-modules/products-device-support-tables-list.html.
Switch Power Input Requirements
The following table lists the typical amount of power that the switch consumes. It also lists the maximum
amount of power that you must provision for the switch and power supply for peak conditions.
Note
Some power supplies have UL listed capabilities that are greater than the maximum power requirements for
a switch. To determine the power consumption characteristics for the switch, use the typical and maximum
requirements that are listed in the following table.
Switch
Cisco Nexus C9316D-GX
Cisco Nexus C9316D-GX ACI-Mode Switch Hardware Installation Guide
34
Weight per Unit
—
2.42 lb (1.1 kg)
Typical Power
Maximum Power
Consumption (AC or DC)
Consumption (AC or DC)
420 W
1010 W
System Specifications
Quantity
2 (1 for operations and 1 for
redundancy)
https://www.cisco.com/
https://www.cisco.com/c/en/us/support/
Heat Dissipation
Requirement
3,466.22 BTUs per hour