Grounding Requirements Planning for Power Requirements Airflow Requirements Rack and Cabinet Requirements Clearance Requirements C H A P T E R 3 Installing the Chassis Safety Installation Options with Rack-Mount Kits Airflow Considerations Cisco Nexus C9316D-GX ACI-Mode Switch Hardware Installation Guide...
Page 4
Switch Dimensions Switch and Module Weights and Quantities Transceiver and Cable Specifications Switch Power Input Requirements Power Specifications 1100-W AC Power Supply Specifications 1100-W HVAC/HVDC Power Supply Specifications 1100-W DC Power Supply Specifications Cisco Nexus C9316D-GX ACI-Mode Switch Hardware Installation Guide...
Page 5
A P P E N D I X C LEDs Switch Chassis LEDs Fan Module LEDs Power Supply LEDs A P P E N D I X D Additional Kits Rack Mount Kit NXK-ACC-KIT-1RU Cisco Nexus C9316D-GX ACI-Mode Switch Hardware Installation Guide...
• Documentation Feedback, on page viii • Communications, Services, and Additional Information, on page viii Audience This publication is for network administrators who install, configure, and maintain Cisco Nexus switches. Documentation Conventions Command descriptions use the following conventions: Convention Description...
Cisco Bug Search Tool Cisco Bug Search Tool (BST) is a web-based tool that acts as a gateway to the Cisco bug tracking system that maintains a comprehensive list of defects and vulnerabilities in Cisco products and software. BST provides you with detailed defect information about your products and software.
Overview, on page 1 Overview The Cisco Nexus 9316D-GX switch (N9K-C9316D-GX) is a 1-RU, fixed-port switch designed for deployment in data centers. This switch has 16 x 400/100-Gbps QSFP-DD ports. To determine how to use and configure these ports, see the...
Page 10
The following figure shows the hardware features seen from the port side of the chassis. Figure 1: Port Side View of the Cisco Nexus 9316D-GX Switch Chassis LEDs (Beacon [BCN], Status [STS], and...
Page 11
The following figure shows the hardware features seen from the power supply side of the chassis. Figure 2: Power Supply Side View of the Cisco Nexus 9316D-GX Switch Two power supplies (one for operations and one Out-of-band management port (RJ-45 port) for redundancy) (AC power supplies shown).
Page 12
If the switch has port-side exhaust airflow (blue coloring for fan modules), you must locate the ports in the hot aisle. If you locate the air intake in a hot aisle, the switch can overheat and shut down. Cisco Nexus C9316D-GX ACI-Mode Switch Hardware Installation Guide...
Altitude Requirements Altitude rating is based on power supply installed; see critical components list in the system CB report for altitude rating. Cisco Nexus C9316D-GX ACI-Mode Switch Hardware Installation Guide...
The wiring is unlikely to emit radio interference if you use a twisted-pair cable with a good distribution of grounding conductors. If you exceed the recommended distances, use a high-quality twisted-pair cable with one ground conductor for each data signal when applicable. Cisco Nexus C9316D-GX ACI-Mode Switch Hardware Installation Guide...
Planning for Power Requirements The switch includes two power supplies (1-to-1 redundancy with current sharing) in one of the following combinations: • Two 1100-W AC power supplies • Two 1100-W DC power supplies Cisco Nexus C9316D-GX ACI-Mode Switch Hardware Installation Guide...
Page 16
(rated 240-380VDC). Note We recommend 8-AWG wire for DC installations in the U.S. Note For the power cables to use with the power supplies, see Power Cable Specifications, on page Cisco Nexus C9316D-GX ACI-Mode Switch Hardware Installation Guide...
(for proper mounting of the bottom-support brackets or other mounting hardware). Also, you must have power receptacles that are located within reach of the power cords that are used with the switch. Cisco Nexus C9316D-GX ACI-Mode Switch Hardware Installation Guide...
Width of the front clearance area (equal to the width of the chassis with two rack-mount brackets that are attached to it). Note Both the front and rear of the chassis must be open to both aisles for airflow. Cisco Nexus C9316D-GX ACI-Mode Switch Hardware Installation Guide...
Starting the Switch, on page 19 Safety Before you install, operate, or service the switch, see the Regulatory, Compliance, and Safety Information for the Cisco Nexus 3000 and 9000 Series for important Safety Information. Warning Statement 1071 Warning Definition IMPORTANT SAFETY INSTRUCTIONS This warning symbol means danger.
You can install the switch using the following rack-mount options: • Rack-mount kit (NXK-ACC-KIT-1RU) which you can order from Cisco. This option offers you easy installation, greater stability, increased weight capacity, added accessibility, and improved removability with front and rear removal.
Page 21
This product relies on the building's installation for short-circuit (overcurrent) protection. Ensure that the protective devices is rated not greater than 40A for the regular DC power supplies (rated 48-60VDC) and 10A for the HVDC power supplies. Cisco Nexus C9316D-GX ACI-Mode Switch Hardware Installation Guide...
You must supply the eight 10-32 or 12-24 screws required to mount the slider rails and switch to the rack. Before you begin • You have inspected the switch shipment to ensure that you have everything ordered. Cisco Nexus C9316D-GX ACI-Mode Switch Hardware Installation Guide...
Page 23
The holes that you use depend on the requirements of your rack and the amount of clearance required for interface cables (3 inches [7.6 mm] minimum) and module handles (1 inch [2.5 mm] minimum). Cisco Nexus C9316D-GX ACI-Mode Switch Hardware Installation Guide...
Page 24
Holding the switch with both hands, position the two rear rack-mount brackets on the switch between the rack or cabinet posts that do not have slider rails attached to them (see the following figure). Cisco Nexus C9316D-GX ACI-Mode Switch Hardware Installation Guide...
Page 25
Tighten the 10-32 screws to 20 in-lb (2.26 N·m) or tighten the 12-24 screws to 30 in-lb (3.39 N·m). Step 5 If you attached a grounding wire to the chassis grounding pad, connect the other end of the wire to the facility ground. Cisco Nexus C9316D-GX ACI-Mode Switch Hardware Installation Guide...
Verify that the ground wire is securely attached to the grounding lug by attempting to pull the wire out of the crimped lug. Chassis grounding pad 2 M4 screws are used to secure the grounding lug to the chassis Cisco Nexus C9316D-GX ACI-Mode Switch Hardware Installation Guide...
Make sure that the connector clicks when fully pushed into the receptacle. b) Connect the other end of the power cable to a power source. Cisco Nexus C9316D-GX ACI-Mode Switch Hardware Installation Guide...
Page 28
A setup utility automatically launches the first time that you access the switch and guides you through the basic configuration. For instructions on how to configure the switch and check module connectivity, see the appropriate Cisco Nexus 9000 Series configuration guide.
When running cables in overhead or subfloor cable trays, we strongly recommend that you locate power cables and other potential noise sources as far away as practical from network cabling that terminates on Cisco equipment. In situations where long parallel cable runs cannot be separated by at least 3.3 feet (1 meter), we recommend that you shield any potential noise sources by housing them in a grounded metallic conduit.
Page 30
Connect the other end of the RJ-45 rollover cable to the console or to a modem. What to do next You are ready to create the initial switch configuration (see Creating the Initial Switch Configuration, on page 23). Cisco Nexus C9316D-GX ACI-Mode Switch Hardware Installation Guide...
To connect the switch to the network, you can use the default choices for each configuration except the IP address, which you must provide. You can perform the other configurations later as described in the Cisco Nexus 9000 Series NX-OS Fundamentals Configuration Guide.
RJ-45 connectors. For longer connections, you can use an optical cable with SFP transceivers (LH or SX type). Note Use only one of these management ports—the switch does not support the use of both management ports. Cisco Nexus C9316D-GX ACI-Mode Switch Hardware Installation Guide...
When removing transceivers from the switch, it is best to remove the optical cable first and then remove the transceiver. To determine which transceivers, adapters, and cables are supported by this switch, see the Cisco Transceiver Modules Compatibility Information document. Cisco Nexus C9316D-GX ACI-Mode Switch Hardware Installation Guide...
Page 34
Connecting the Switch to the Network Connecting Interface Ports to Other Devices Cisco Nexus C9316D-GX ACI-Mode Switch Hardware Installation Guide...
• There must be an earth ground connection to the chassis that you are installing the replacement module. AC power supplies connected to AC power sources are automatically grounded through their power cable. Cisco Nexus C9316D-GX ACI-Mode Switch Hardware Installation Guide...
Page 36
Depending on the outlet receptacle on your power distribution unit, you might need the optional jumper Note cable to connect the switch to your outlet receptacle. e) Verify that the power supply is operational by making sure that the power supply LED is green. Cisco Nexus C9316D-GX ACI-Mode Switch Hardware Installation Guide...
• Standard 19-inch (48.3 cm) (two- or four-post EIA cabinet or rack, with mounting rails that conform to English universal hole spacing per section 1 of ANSI/EIA-310-D-1992). For more information, see Requirements Specific to Perforated Cabinets, on page Cisco Nexus C9316D-GX ACI-Mode Switch Hardware Installation Guide...
• The roof should be perforated with at least a 20 percent open area. • The cabinet floor should be open or perforated to enhance cooling. The Cisco R Series rack conforms to these requirements. Cisco Nexus C9316D-GX ACI-Mode Switch Hardware Installation Guide...
To help with cable management, you might want to allow additional space in the rack above and below the chassis to make it easier to route all of the fiber optic or copper cables through the rack. Cisco Nexus C9316D-GX ACI-Mode Switch Hardware Installation Guide...
Switch Typical Power Maximum Power Heat Dissipation Consumption (AC or DC) Consumption (AC or DC) Requirement Cisco Nexus C9316D-GX 420 W 1010 W 3,466.22 BTUs per hour Cisco Nexus C9316D-GX ACI-Mode Switch Hardware Installation Guide...
Form factor RSP1 1100-W HVAC/HVDC Power Supply Specifications These specifications apply to the following power supplies: • NXA-PHV-1100W-PE • NXA-PHV-1100W-PI Characteristic Specification Efficiency Input voltage 100VAC – 277VAC, 240VDC – 380VDC Cisco Nexus C9316D-GX ACI-Mode Switch Hardware Installation Guide...
Power Cable Specifications The following sections specify the power cables that you can order and use with this switch. Regulatory Standards Compliance Specifications The following table lists the regulatory standards compliance for the switch. Cisco Nexus C9316D-GX ACI-Mode Switch Hardware Installation Guide...
Page 45
• CNS13438 Class A EMC: Immunity • EN55024 • CISPR24 • EN300386 • KN 61000-4 series RoHS The product is RoH-6 compliant with exceptions for leaded-ball grid-array (BGA) balls and lead press-fit connectors. Cisco Nexus C9316D-GX ACI-Mode Switch Hardware Installation Guide...
Page 46
System Specifications System Specifications Cisco Nexus C9316D-GX ACI-Mode Switch Hardware Installation Guide...
Temperature exceeds the major alarm threshold. The switch is not receiving power. Green Fans and power supply modules are operational. Amber At least one fan or power supply module is not operating. Cisco Nexus C9316D-GX ACI-Mode Switch Hardware Installation Guide...
Power supply is connected to a power source but not outputting power to the green switch. Green Flashing amber Power supply warning—possibly one of the following conditions: • High voltage • High power • Low voltage • Slow power supply fan Cisco Nexus C9316D-GX ACI-Mode Switch Hardware Installation Guide...
Page 49
Amber Rotor fault Note This behavior occurs if the fan rotor is stopped during normal switch operation. Amber AC cord that is removed while in redundant mode (while other PSU is running). Cisco Nexus C9316D-GX ACI-Mode Switch Hardware Installation Guide...
Not applicable Hazardous substances list for customers in China The following table lists and illustrates the console cable (CAB-CONSOLE-RJ45) that can be ordered. Illustration Description Quantity Console cable with DB-9F and RJ-45F connectors Cisco Nexus C9316D-GX ACI-Mode Switch Hardware Installation Guide...