Drain pipe and Drain hose Installation

Care must be taken when installing the drain hose for the indoor unit to ensure that any condensate water is correctly
drained outside. The drain hose can be installed to the right or left side of the base pan.
1. Unscrew the 4 tapped screws to remove the cover of the drain hose
connection port.
2. Insert the flexible hose to the drain hose port.
Fix the flexible hose to the indoor unit with the supplied
cable clamp securely.
NOTE
(Use the screwdriver to fix the flexible hose securely.)
3. Install the drain hose so that its length can be as short as possible.
Internal diameter of the drain hose should be the same or slightly
bigger than the external diameter of the drain hose port.
Inner diameter of the drain hose
32mm(Inner diameter)
Give a slightly slant to the drain hose for proper drainage
of condensate.
NOTE
Fix the flexible hose to the PVC with the supplied cable tie
securely.
4. Wrap the drain hose with the insulation drain as shown in figure and
secure it.
NASA_Big Duct_AM@@@FNHDEH@_IM_03864A-05_EN.indd 17
Drain hose connection port
Cable Clamp
Cable-tie
Clamp hose
Indoor Unit
Insulation
Fiexible hose
Must fit tightly against
body without any gap.
CAUTION
No gap