FUEL PUMP
TO GENERATOR SET
FS-1082
FIGURE 6.
FUEL PUMP CONNECTIONS
be covered when the hood is down. See Figure 7.
Holes are pre-drilled in the panel.
9. To lock the gasoline tank shield, push down on
the shield and slide the barrel bolt lock, on the
inside of the compartment panel, through the
hole of the shield part which extends through the
panel. See Figure 7.
REMOTE START-STOP CONNECTIONS
The remote start, home standby model has provi-
sions for remote start and stop connections. Locate
the remote switch in the house, garage or other con-
venient location for starting and stopping the gener-
ating set.
For remote connections to an automatic transfer switch which
automatically starts and stops the generating set, refer to instruc-
tions furnished with the automatic transfer switch.
For the remote switch, use a single-pole, double-
throw, momentary contact, center-off type switch.
You can use #18 wire for distances up to 250 feet (76
meters) from the generating set. Several remote
switches can be used in different locations if they are
wired in parallel.
Use a momentary-contact, start-stop switch only. Otherwise, the
exhaust blower used for the gas/gasoline model runs continuously
during the entire operation period (after remote starting).
Remote connections to the generating set are made
according to Figure 8. A wiring harness runs from the
connector located on the side of the control box to
the time delay control located on the rear panel of the
housing (Figure 13). Customer wiring is from time
delay control to the remote momentary contact
switch.
1/4-20 SCREWS, F L A T WASHERS,
LOCKWASHERS AND NUTS
B A R R E L B O L T LOCK
(LOCATED INSIDE
COMPARTMENT PANEL)
TANK HOOD
FIGURE 7.
FUEL TANK HOOD INSTALLATION
7