Commissioning And Periodic Testing; Maintenance; Troubleshooting - Greenheck DFD Series Installation, Operation And Maintenance Manual

Curtain fire dampers
Table of Contents

Advertisement

Damper Commissioning and Periodic Testing
The International Fire Code (IFC) requires fire dampers to be maintained in accordance with NFPA standard 80 and
smoke dampers to be maintained in accordance with NFPA standard 105. NFPA 80 and 105 define the frequency
and method for periodically testing life safety dampers.
NFPA 80 & 105 do not require heat to be applied to a damper's fusible link or thermostat during periodic testing.
Electric or pneumatic actuated dampers are required to be tested by temporarily removing electrical or pneumatic
power from the actuator to ensure the damper fully closes and then fully opens once power is restored. Mechanical
and gravity operated dampers utilizing a fusible link are required to be tested by removing the fusible link and
allowing the damper to fully close and then manually reopening the damper. Re-install the fusible link.
Greenheck's life safety dampers shall not be tested by applying heat with uncontrollable heat sources (i.e. heat guns,
torches, etc.) as this can permanently damage the thermostat or other parts of the damper.
Damper Maintenance
Dampers do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, use
mild detergents or solvents. If lubrication is desired for components such as axle bearings, jackshaft bearings and
jamb seals, do not use oil-based lubricants or any other lubricants that attract contaminants such as dust.
Dampers and their actuator(s) must be maintained, cycled, and tested a minimum in accordance with:
• The latest editions of NFPA 80, 90A, 92, 101, 105, UL864, AMCA 503-03 and local codes.
• Actuator manufacturer recommendations.
Damper Troubleshooting
The following is a possible cause and correction list for common concerns with the dampers.
Symptom
Damper does not fully
open and/or close
RRL or TOR sensor
tripped
Damper does not
operate
Our Commitment
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications
without notice.
Product warranties can be found online at Greenheck.com, either on the specific product page or in the literature
section of the website at Greenheck.com/Resources/Library/Literature.
®
Phone: 715.359.6171 • Fax: 715.355.2399 • Parts: 800.355.5354 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com
12
481318 • FSD DFD FSD-3xxV, Rev. 8, January 2020
Possible Cause
Frame is 'racked' causing blades to bind
on jamb seals
Actuator linkage loose
Defective motor
Screws in damper linkage
Contaminants on damper
Heat
No power supplied to the actuator
Corrective Action
Adjust frame such that it is square and plumb
Close damper, disconnect power, adjust and tighten
linkage
Replace
Damper installed too far into wall. Move out to line as
designated on damper label
Clean with a non-oil based solvent (see Damper

Maintenance)

Push reset button located on backside of RRL or TOR
Add power supply
Copyright 2020 © Greenheck Fan Corporation

Advertisement

Table of Contents
loading

Table of Contents