Greenheck FD 150X Installation, Operation And Maintenance Instructions
Greenheck FD 150X Installation, Operation And Maintenance Instructions

Greenheck FD 150X Installation, Operation And Maintenance Instructions

1 1/2 hour curtain fire dampers vertical or horizontal mount

Advertisement

Quick Links

Installation, Operation and Maintenance Instructions
InStALLAtIon SUPPLEmEntS
Refer to the appropriate Greenheck installation
supplements for special requirements:
Support Mullions
Shaftwall Supplement
Drywall Supplement
Grille Installation Supplement
Drive Slip Supplement
Sealant Supplement
Sleeve Extension Supplement
Single sinde Retaining Angles Supplement
Note: Refer to Greenheck IOM, Part #461335, for
CFSD models to be installed in corridor ceiling
applications.
RECEIvIng AnD HAnDLIng
Upon receiving dampers, check for both obvious and
hidden damage. If damage is found, record all necessary
information on the bill of lading and file a claim with the
final carrier. Check to be sure that all parts of the shipment,
including accessories, are accounted for.
Dampers must be kept dry and clean. Indoor storage
and protection from dirt, dust and the weather is highly
recommended. Do not store at temperatures in excess of
100°F.
This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the job
is complete.
Due to continuing research, Greenheck reserves the right to change specifications without notice.
FD & DFD 150X moDELS
vertical or Horizontal mount
FD and DFD 150X Series models are intended for
installation in accordance with fire damper requirements
established by:
national Fire Protection Association
NFPA Standard 80, 90A, & 101
IBC International Building Codes
CSFm California State Fire marshal
Fire Damper Listing (#3225-0981:102)
new York City (BSA/MEA listing #260-91-M)
"UL CLASSIFIED (see complete marking on product)"
"UL CLASSIFIED to Canadian safety standards (see
complete marking on product)"
UL Standard 555 (Listing #R13317)
SAFEtY WARnIng:
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, injury
or death. Read the installation, operating, and
maintenance instructions thoroughly before installing
or servicing this equipment.
WARRAntY
Greenheck warrants this equipment to be free from
defects in material and workmanship for a period of one
year from the purchase date. Any units or parts which
prove to be defective during the warranty period will be
repaired or replaced at our option. Greenheck shall not
be liable for damages resulting from misapplication or
misuse of its products. Greenheck will not be responsible
for any installation or removal costs. Greenheck will not be
responsible for any service work or backcharges without
prior written authorization.
Part number 453946
1
1
Curtain Fire Dampers
Hour
2

Advertisement

loading

Summary of Contents for Greenheck FD 150X

  • Page 1 This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the job is complete. Due to continuing research, Greenheck reserves the right to change specifications without notice.
  • Page 2 table of Contents Pre-Installation Guidelines ............................2 Installation ................................3-4 Breakaway Connections ............................5 Damper Maintenance ..............................6 Damper Troubleshooting ............................6 Installation for Steel Stud Connection Option ....................... 6-7 Pre-Installation guidelines The basic intent of a proper installation is to secure the fire damper in, not to, the opening in such a manner as to prevent distortion and disruption of damper operation.
  • Page 3: Installation

    • Galvanized steel fire dampers and sleeves: 1/8 in. (3mm) per linear foot of damper width and height with a minimum clearance of 1/4 in. (6mm) .Recommended clearances, for width and/or height dimensions of: 1 ) 48 in. (1219mm) or less: 1/2 in. (13mm) clearance 2 ) More than 48 in. (1219mm) and 96 in. (2438mm) or less: 1 in. (25mm) clearance 3 ) More than 96 in. (2438mm): 11/2 in. (38mm) clearance These are total clearances (ignoring fastener heads) and do not need to be equally spaced around the damper.
  • Page 4: Installation

    Maximum Sizes Maximum Overall for Single Section Size for Multi- Damper Model Dampers* Section Dampers* Retaining Angles in. (mm) in. (mm) (See Section 4) FD-150X (H or V) 48 x 48 (1219 x 1219) 96 x 48 or 120 x 40 ((2438 x 1219) or See Section 2 (3048 x 1016)
  • Page 5: Breakaway Connections

    Figure 5: Detail of retaining angles and gypsum board application for metal and wooden stud construction. Duct-Sleeve Connections traditional Breakaway Style transverse Joints Transverse joints illustrated in Figure 6 have always been approved as breakaway connections. SMACNA testing has also approved the following variations as breakaway connections.
  • Page 6 (tDC by Lockformer, tDF by Engle) TDC and TDF systems are approved as breakaway connections when installed as described in the SMACNA Duct Construction Standards. Standard 6 in. metal clips may be used with spacing (see Figure 8). Three-eighth in. metal bolts and nuts may be used to fasten together corner pieces (see Figure 9). Duct End Flange Corner Piece 3/8 in. bolt (optional) Figure 9: Detail of bolted corner. Figure 8: Detail of proprietary flanged system breakaway connections.
  • Page 7: Damper Maintenance

    Adjust frame such that it is square and plumb Screws in damper linkage Locate screws and remove Damper does not fully open and/or fully close Contaminant's on damper Clean with a non-oil based solvent (see Damper Maintenance) Link separated Heat Replace link Copyright © 2008 Greenheck Fan Corporation 453946 FD/DFD 150X series R12 December 2008...