Introduction

2
These heaters must not be installed in wet rooms
or other high humidity areas.
3
3
These heaters are designed for use on standard
two-pipe pumped central heating systems with
4
a maximum water temperature of 86°C and a
maximum pressure of 6 bar (88lbs/in.).
6
Pipe connections to heat-exchanger are 22mm.
8
Flow and return connection must be observed,
9
see labelling.
10
These heaters are classified as a fixed appliance
12
and the electrical connection should be via a 3A
fused spur. The fused spur must not be directly
14
below the heater but should be accessible after
completion of the installation. All heaters must
15
be earthed.
16
To avoid the possibility of vibration these units
14
must be fitted to a flat even surface.
18
Please note that the guarantee may be invalidated
if this product is not installed and used in
22
accordance with these instructions.
22
Note: 15mm pipe may be used for heating
capacities of up to 12kW. (This is subject to
23
compliance with CIBSE recommendations)
23
23
23