Technical Characteristics; Installation - Re US3 User Manual

Ultrasonic sensor
Table of Contents

Advertisement

Re
S.p.A.

Technical characteristics

Operating frequency:
Minimum measuring distance: 150mm at 25°C (160mm at 50°C )
Maximum measuring distance: 1800mm
Operating mode:
2 analog outputs:
Setpoint analog input
10V reference voltage for setpoint external potentiometer connection
Software filter to prevent sudden changes in distance
2 digital outputs for alarms with programmable threshold
10-position multi-purpose LED bar
Target present indicator
Automatic compensation of change in speed of sound with temperature
RS-485 for connection to Personal Computer
Power supply:

Installation

To ensure that the device is installed efficiently, follow the instructions below:
1. Even if the device can function properly at a voltage that varies between 18 and 30Vdc, always supply
a stabilised voltage that is not affected by network load variations.
2. Never leave a break in the cable shielding. If a connector or joint has to be inserted in the US3
cable, make the connection as shown as shown in the diagram:
3. The CLAMP ferrite provided with the equipment must be applied to the cable.
Rev.12/04/11
125kHz
(for materials which absorb sound: this is reduced in proportion to
the degree to which the material absorbs sound)
- Diameter reader / Regulator (resolution 0.5mm)
- Proportional diametral output 0-10V
- Regulated diametral output 0-10V or 4-20mA
(possibility of inverting the regulated diametral output)
24V dc
US3
4/23