® 16HX-FT Battery Installation, Operation and Maintenance Instructions Visit us at www.enersys.com...
Page 2
The necessity of a charge can also be determined by measuring the open ■ Stowing circuit voltage of a stored battery. For proper installation, EnerSys battery racks and cabinets are ® Charging is advised if the voltage drops below 2.07 Vpc (16.56 Vpb).
Page 3
6. Discharging ■ Torque Tighten the M8 connector bolts between 100 and 110 in-lbs (11.3 to 12.5 ■ End of Discharge Voltage The end of discharge voltage must be limited to a minimum value of 1.60 Vpc N•m). A loose connector can cause problems in charger adjustment, (12.8 Vpb).