EnerSys DataSafe 16HX FT Series Installation, Operation And Maintenance Instructions

EnerSys DataSafe 16HX FT Series Installation, Operation And Maintenance Instructions

Advertisement

Quick Links

®
16HX-FT
Battery Installation, Operation and
Maintenance Instructions
Visit us at www.enersys.com

Advertisement

loading

Summary of Contents for EnerSys DataSafe 16HX FT Series

  • Page 1 ® 16HX-FT Battery Installation, Operation and Maintenance Instructions Visit us at www.enersys.com...
  • Page 2 The necessity of a charge can also be determined by measuring the open ■ Stowing circuit voltage of a stored battery. For proper installation, EnerSys battery racks and cabinets are ® Charging is advised if the voltage drops below 2.07 Vpc (16.56 Vpb).
  • Page 3 6. Discharging ■ Torque Tighten the M8 connector bolts between 100 and 110 in-lbs (11.3 to 12.5 ■ End of Discharge Voltage The end of discharge voltage must be limited to a minimum value of 1.60 Vpc N•m). A loose connector can cause problems in charger adjustment, (12.8 Vpb).
  • Page 4 Singapore 189721 +1-800-538-3627 Switzerland Tel: +65 6508 1780 © 2017 EnerSys. All rights reserved. Trademarks and logos are the property of EnerSys and its affiliates, except Nord-Lock, which is not the property of EnerSys. Subject to revisions without prior notice. E.&O.E.