EnerSys DataSafe 16HX FT Series Installation, Operation And Maintenance Instructions

EnerSys DataSafe 16HX FT Series Installation, Operation And Maintenance Instructions

Advertisement

Quick Links

®
16HX-FT
Battery Installation, Operation and
Maintenance Instructions
Visit us at www.enersys.com

Advertisement

loading
Need help?

Need help?

Do you have a question about the DataSafe 16HX FT Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for EnerSys DataSafe 16HX FT Series

  • Page 1 ® 16HX-FT Battery Installation, Operation and Maintenance Instructions Visit us at www.enersys.com...
  • Page 2 The necessity of a charge can also be determined by measuring the open ■ Stowing circuit voltage of a stored battery. For proper installation, EnerSys battery racks and cabinets are ® Charging is advised if the voltage drops below 2.07 Vpc (16.56 Vpb).
  • Page 3 6. Discharging ■ Torque Tighten the M8 connector bolts between 100 and 110 in-lbs (11.3 to 12.5 ■ End of Discharge Voltage The end of discharge voltage must be limited to a minimum value of 1.60 Vpc N•m). A loose connector can cause problems in charger adjustment, (12.8 Vpb).
  • Page 4 Singapore 189721 +1-800-538-3627 Switzerland Tel: +65 6508 1780 © 2017 EnerSys. All rights reserved. Trademarks and logos are the property of EnerSys and its affiliates, except Nord-Lock, which is not the property of EnerSys. Subject to revisions without prior notice. E.&O.E.