5.7.3. Connection inputs of the OR logic ............. 23 Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany Mixed gas sensor KNX VOC-UP basic • from software version 0.3.6, ETS programme version 1.1 • Version: 27.01.2020 • Technical changes reserved. Errors reserved.
Page 4
The change status (software version and date) can be found in the contents footer. If you have a device with a later software version, please check www.elsner-elektronik.de in the menu area "Service" to find out whether a more up-to- date version of the manual is available.
• Socket Ø 60 mm, 42 mm deep • Frame (for element 55 x 55 mm), suitable for the switching programme used in the building Mixed Gas Sensor KNX VOC-UP basic • Version: 27.01.2020 • Technical changes reserved. Errors reserved.
After unpacking the device, check it immediately for possible mechanical damage. If it has been damaged in transport, inform the supplier immediately. Mixed Gas Sensor KNX VOC-UP basic • Version: 27.01.2020 • Technical changes reserved. Errors reserved.
To ensure a correct VOC measurement, the device must be installed in a windproof socket. 2.3. Composition 2.3.1. Housing Fig. 1 Notches Air circulation holes Programming LED (recessed) Programming button (recessed) for teaching instrument Air circulation holes (BOTTOM) Mixed Gas Sensor KNX VOC-UP basic • Version: 27.01.2020 • Technical changes reserved. Errors reserved.
The device is supplied with the bus address 15.15.255. You can program another address into the ETS by overwriting the 15.15.255 address or by teaching via the programming button. Mixed Gas Sensor KNX VOC-UP basic • Version: 27.01.2020 • Technical changes reserved. Errors reserved.
• 1 message per second • ... • 5 messages per second • ... • 20 messages per second Use VOC malfunction object Yes • No Mixed gas sensor KNX VOC-UP basic • Version: 27.01.2020 • Technical changes reserved. Errors reserved.
5000 ppm Maximum allowable concentration 5.4.1. VOC threshold value 1, 2, 3, 4 The settings options for temperature, humidity and CO2 threshold values are the same. Mixed gas sensor KNX VOC-UP basic • Version: 27.01.2020 • Technical changes reserved. Errors reserved..
Page 17
Set the behaviour of the switching output when a threshold value is exceeded/under- cut. The output switching delay can be set using objects or directly as a parameter. Mixed gas sensor KNX VOC-UP basic • Version: 27.01.2020 • Technical changes reserved. Errors reserved.
Page 18
• Do not send message • If switching output = 0 send 0 Switching output sends on change and Send switching output status periodically Mixed gas sensor KNX VOC-UP basic • Version: 27.01.2020 • Technical changes reserved. Errors reserved..
If you activate the control, you can use the following settings to define control type, tar- get values, and ventilation. Use control Yes • No General control The Mixed gas sensor KNX VOC-UP basic can be used to control one or two-stage ventilation. Type of control • One-stage ventilation • Two-stage ventilation Configure a block for the ventilation control using the blocking object.
Page 20
1 • 2 • 5 • ... • 20 • ... • 100 • 200 (upon increase/decrease change) Ventilation control Depending on the control mode, one and/or two setting sections for the ventilation stages are displayed. Mixed gas sensor KNX VOC-UP basic • Version: 27.01.2020 • Technical changes reserved. Errors reserved..
Send behaviour and blocks can also be set. Output delivered • Maximum value • Minimum value • Average value Use input 1/2/3/4/5 No • Yes Mixed gas sensor KNX VOC-UP basic • Version: 27.01.2020 • Technical changes reserved. Errors reserved.
Object value prior to 1. communication for: Logic input 1... 16 0 • 1 AND logic Logic 1/2/3/4/5/6/7/8 not active • active OR logic Logic 1/2/3/4/5/6/7/8 not active • active Mixed gas sensor KNX VOC-UP basic • Version: 27.01.2020 • Technical changes reserved. Errors reserved..
• at value 1: block | at value 0: release • at value 0: block | at value 1: release Blocking object value before 1st communi- 0 • 1 cation Mixed gas sensor KNX VOC-UP basic • Version: 27.01.2020 • Technical changes reserved. Errors reserved.