(ppm). 1000ppm cor- respond to 0.1%. From this value on humans perceive the room air as „used“. Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
±10% of the measured value or ±75 ppm (whatever is greater) Measurement range -40…+100°C temperature Resolution (temperature) 0.1°C Accuracy (temperature) ± 0.4°C at 25°C Measurement range 0…100% humidity Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
Page 6
EN 60730-1:2000 Section EMV (23, 26, H23, H26) • EN 50090-2-2:1996-11 + A1:2002-01 • EN 61000-6-1:2004 The product has been tested for the above mentioned standards by an accredited EMV laboratory. Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
Elsner Elektronik does not assume any liability for changes in standards after publica- tion of this instruction manual. 2.2. Installation position The KNX AQS/TH is flush mounted in a distribution box (Ø 70 mm, 36 mm deep) and covered. Box and cover are supplied. For monitoring of the CO content of the room air choose an installation position in height of head (standing or sitting, according to utilization of room).
2.3.1. Front view sensor board Grooves for attachment of cover Oblong holes for fastening with distribution box Programming LED Programming button for teaching the device Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
The future orientation is already determined by fitting the box! Vertical orientation: Logo on bottom of board Logo on bottom of cover Screw holes on left and right Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
An LED inside the sensor will flash in regular intervals during operation. The flashing is visible in the dark through the punched pattern of the cover. Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
Temp. threshold value 1: Switching Input 1.002 output block Temp. threshold value 2: Absolute Input / output 9.001 C R W T U value Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
Page 12
Temp. control: Target value, Cooling Input / output 9.001 C R W T U Temp. control: Target value, Cooling Input 1.002 day (1:+ | 0:-) Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
Page 13
Output 9.007 C R T humidity Maximum measured value for Output 9.007 C R T humidity Reset min./max. measured value for Input 1.017 humidity Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
Page 14
C R T tion (1=ON | 0=OFF) Dew point temperature Output 9.001 C R T Cooling medium temp.: Threshold Output 9.001 C R T value Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
Page 15
0 to 1 CO2 threshold value 2: Switching Input 7.005 delay from 1 to 0 CO2 threshold value 2: Switching out- Output 1.001 C R T Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
Page 17
AND Logic 6: 8 Bit Output A Output 5.010 C R T AND Logic 6: 8 Bit Output B Output 5.010 C R T Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
Page 18
OR Logic 8: 8 Bit Output A Output 5.010 C R T OR Logic 8: 8 Bit Output B Output 5.010 C R T Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
1 • 2 • 3 • 5 • 10 • 20 Telegrams per second Use temperature/humidity malfunction No • Yes object Use CO2 malfunction object No • Yes Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
Ext. measured value proportion of the total 5% … 100% (in steps of 5%) measured value All following settings refer to the total measured value Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
No • Yes (Values are not maintained after reset) 4.3. Temperature threshold values Use threshold value 1 / 2 / 3 / 4 No • Yes Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
If the threshold value is set per Parameter: Threshold value setpoint per Parameter Threshold value in 0,1°C -300… 800 Hysteresis of the threshold value in % 0 … 50 Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
Page 24
Limitation of object value (min) in 0,1°C -300 … 800 Limitation of object value (max) in 0,1°C -300 … 800 Type of threshold change • Absolute value • Increment/decrement Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
Page 25
Send switching output in a cycle of 5 s • 10 s • 30 s • 1 min • … • 2 h (only if sending „periodically“) Blocking: Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
Page 26
1 and periodically (no selection) if switching output = 0 send 0 on change to 0 and periodically (no selection) Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
• on change and periodically Transmission cycle 5 s • 10 s • 30 s • 1 min • … • 2 h (only if sending „periodically“) Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
Page 28
Parameter • Communication object If the target value is set per Parameter: Target value setpoint per Parameter Target value in 0,1°C -300 … 800 Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
Page 30
• send a specific value Value in % (only if sending a specific value) 0 ... 100 With release the actuating variable follows the control Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
Page 31
(only if the controller is set by „controler parameter“ ) Re-setting time in minutes 1 … 255 (only if the controller is set by „controler parameter“ ) Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
Page 32
• send a specific value Value in % (only if sending a specific value) 0 ... 100 With release the actuating variable follows the control Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
Page 33
The value communicated last shall be • not maintained • After restoration of voltage • After restoration of voltage and pro- gramming (Do not use for first commis- sioning) Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
• 1 s • 2 s • 5 s • 10 s • … • 2 h (after opening window) Status of window before 1. communication CLOSED • OPEN 4.5. Humidity measured value Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
Use minimum and maximum value No • Yes (Values are not maintained after reset) 4.6. Humidity threshold values Use humidity threshold values 1 / 2 No • Yes Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
1. communication (only if the value communicated last is „not“ maintained or „after restoration of voltage“) Type of threshold change • Absolute value • Increment/decrement Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
Page 37
Evaluation of the blocking object • if value 1: block | if value 0: release • if value 0: block | if value 1: release Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
1 and periodically (no selection) if switching output = 0 send 0 on change to 0 and periodically (no selection) 4.7. Humidity PI control Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
Page 39
Controler target value: Target value setpoint per Parameter • Communication object If the target value is set per Parameter: Target value setpoint per Parameter Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
Page 40
0 … 100 Type of threshold change • Absolute value • Increment/decrement Step size 1,0% • 2,0% • 5,0% • 10,0% (only if sending „Increment/decrement“) Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
Page 41
• send a specific value Value in % 0 … 100 (only if sending a specific value) With release the actuating variable follows the control Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
5 s • 10 s • 30 s • 1 min • … • 2 h (only if sending „periodically“) Use monitoring of the cooling medium No • Yes temperature Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
Setting of parameters 4.8.1. Monitoring of the cooling medium temperature Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
Page 44
Evaluation of the blocking object • if value 1: block | if value 0: release • if value 0: block | if value 1: release Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
= 0 send 0 on change to 0 and periodically (no selection) 4.9. Absolute humidity Use absolute humidity No • Yes Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
5 s • 10 s • 30 s… • 2 h (only if sending „periodically“) Maximum temperature in °C 25 ... 40 (Standard 26°C) Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
Hysteresis of the absolute humidity: 2 g/kg 4.11. CO2 measured value Offset in ppm -100 … +100 Use external measured value No • Yes Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
Page 48
5 s • 10 s • 30 s • 1 min • … • 2 h (only if sending „periodically“ ) Use maximum value No • Yes (Values are not maintained after reset) Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
Setting of parameters 4.12. CO2 threshold values Use threshold value 1 / 2 / 3 / 4 No • Yes Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
If the threshold value is set per Parameter: Threshold value setpoint per Parameter Threshold value in ppm 0 … 5000 Hysteresis of the threshold value in % 0 … 50 Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
Page 51
• if value 1: block | if value 0: release • if value 0: block | if value 1: release Value of the blocking object 0 • 1 before 1. communication Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
= 0 send 0 on change to 0 and periodically (no selection) 4.13. CO2 PI control Use control No • Yes Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
Page 53
Parameter • Communication object If the target value is set per Parameter: Target value setpoint per Parameter Target value in ppm 400 … 5000 Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
Page 54
Step size in ppm 1 • 2 • 5 • 10 • 20 • 50 • 100 • 200 (only with „Increment/Decrement“) Control of ventilation 1st stage: Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
Value in % (only if a specific value is sent) 0 … 100 With release, the actuating variable follows the control 4.14. Actuating variable comparator Use comparator 1 / 2 No • Yes Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
Evaluation of the blocking object • if value 1: block | bei Wert 0: release • if value 0: block | bei Wert 1: release Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
• the current value after reception of an object 4.15. Logic Use logic inputs No • Yes Object value before 1. communication for Logic input 1 ... 16 0 • 1 Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
• active OR Logic: Logik 1 / 2 / 3 / 4 / 5 / 6 / 7 / 8 not active • active Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
Page 59
• Angle (0°... 360°) • Scene recall (0 ... 127) if logic = 1 Object A Value settings depend on „Type of objects“ Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
Page 60
• send status of the switching output on change of logic and receipt of object send value for current logic status and periodically (no selection) Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
Switching output temperature 2inverted Switching output temperature 3 Switching output temperature 3 inverted Switching output temperature 4 Switching output temperature 4 inverted Temp. control Status switching object Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
Page 62
Switching output CO2 4 inverted CO2 control status ventilation 1 CO2 control status ventilation 1 inverted CO2 control status ventilation 2 CO2 control status ventilation 2 inverted Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
• Angle (0° ... 360°) • Scene recall (0 ... 127) if logic = 1 Object A Value settings depend on „Type of objects“ Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
Page 64
• send status of the switching output on change of logic and receipt of object send value for current logic status and periodically (no selection) Indoor Sensor KNX AQS/TH • Date of issue: 30/09/2010 • Subject to technical changes. Errors excepted.
Need help?