Vents-us MICRA 150 Installation Manual page 3

Air handling unit with heat recovery

Advertisement

8. Open the access door of the unit and remove the
heat recovery core.
CONNECTION TO POWER MAINS
The unit is designed for connection to 120 V / 60 Hz power supply source.
The unit is supplied with a power cable and a plug. The unit must be connected to power mains through a grounded power socket compliant with IEC 60884-1. The power cable is pre-
wired to the terminal block X1 by the manufacturer, fig. 4.
Connect the unit to power mains through the external automatic circuit breaker integrated into the fixed wiring system. Install the circuit breaker to have a free quick access in case of
need to turn the unit off promptly.
The circuit breaker trip current must be in compliance with the current consumption. The recommended circuit breaker rated current is 2.5 A. While selecting the automatic circuit breaker
consider the maximum wire temperature that depends on the wire type, insulation, length and layout way (open wire mounting, channel type or wall-mounted).
Bodor Vents, LLC DBA: VENTS-US
11013 Kenwood Road Cincinnati, Ohio 45242
Phone: (513)348-3853
e-mail: sales@ventsus.com
www.ventsus.com
9. Drill 2 Ø 1⁄4" holes in the wall and mount the unit onto
it using screws and expansion anchors (included into
delivery set).
TWO Ø 4 7/8 " AIR DUCTS
FOUR EXPANSION ANCHORS
AND SCREWS
UNIT
DISCONNECT THE UNIT FROM THE POWER MAINS PRIOR TO ANY OPERATIONS.
THE UNIT MUST BE PLUGGED INTO A PROPERLY INSTALLED POWER SOCKET WITH AN EARTHED TERMINAL.
THE RATED ELECTRICAL PARAMETERS OF THE UNIT ARE SHOWN ON THE RATING PLATE.
ANY TAMPERING WITH THE INTERNAL CONNECTIONS IS PROHIBITED AND WILL VOID THE WARRANTY.
FOUR EXPANSION ANCHORS AND
SCREWS (INCLUDED INTO OUTER
HOOD DELIVERY SET)
OUTER HOOD
Fig. 3. Unit mounting
10. Install the heat recovery core and close the access
door.
MIU_54(MICRA_150)-01