9. SERVICE Menu: (UP + DOWN during Initialization)
9.1 Display:
Language
P- Unit
P- Alarm
Service
9.2 Settings:
• Pressing the SELECT key switches through the Menu (marked with the asterisk).
• Language:
Pressing UP / DOWN keys switches between english and german language.
• P-Unit:
Pressing UP / DOWN keys switches between PSI and BAR as unit for the digital
displayed pressure.
• P-Alarm:
By pressing the UP / DOWN keys, the value for the low pressure alarm-limit can
be selected. If the input pressure is lower than the selected limit, the SC1200
controller switches to ALARM mode and no new dispensing procedure is pos-
sible, as long as the input pressure is less than the selected limit.
• Service:
Service counter – not resetable
10 / 16
SERVICE
: *
E
:
:
BAR
:
5.6 BAR
:
000000239
Spraying System eco-CONTROL SC1200
Commissioning and maintenance manual
Selected language
Selected pressure unit
Selected pressure limit
Service counter