MA7200 PLUS Inverter 1 to 2 HP PID Fan and Pump Quick Start Manual
__________________________________________________________________
Step 8
– Select PID control (Sn-64), and Feedback input (Sn – 24) [4 – 20 mA
or 0 – 10 Vdc]
Before selecting the parameter(s), ensure the inverter is in the STOP mode.
To activate PID control parameter (Sn-64) must be set to =1.
The Feedback Input parameter (Sn –24) is set to = 1 (AIN, 4-20 mA), as factory default. To
select (VIN, 0-10 Vdc), (Sn-24) must be set to 0.
connections)
To set the parameter(s), follow the navigation procedure as shown next.
1 - Press the
2 - Press the
3 - Press the
4 - Press the
5 - Press the
6 - Press the
7 - Press the
________________________________________________________________
(See Figs. 3a, 3b and 3c for feedback
(Turn on PID control)
key
key twice
key until display shows
key
key
key to
.
key to return to the main display.
TECO – Westinghouse Motor Company
Flashing
0
Flashing
1
2 Seconds
Flashing
1
9