Westinghouse Teco MA7200 Plus Quick Start Manual page 16

Ma7200 plus inverter series

Advertisement

MA7200 PLUS Inverter 1 to 2 HP PID Fan and Pump Quick Start Manual
__________________________________________________________________
To set parameter Bn-02 =30.0
Keypad Steps
1 - Press the
EDIT
2 - Press the
ENTER
3 - Press the
RESET
EDIT
4 - Press the
ENTER
5 - Press the
Step 12 – S
etting PID Sleep Function parameters (P1-04), (P2-01),
(P2-02), (P2-03) and (P2-04).
(NOTE: In the case of a Fan application skip this step and go to Step13)
The PID Sleep function is turned on by parameter (P1-04) when set to (=1). This allows the
system to turn off the PID and thus the inverter output so that the pump does not run when
the system level (PSI) is above the set-point. This sleep start level is set by parameter (P2-
01) in a range from 0 – 100% of the maximum inverter output. When the system level drops
below a value (the units are selected by Step 8) set by parameter (P2-03), the sleep
wakeup level, the output of the inverter will turn on. Parameters (P2-02) and (P2-04)
provide delay times in seconds for sleep start level and sleep wakeup level respectively.
Fig. 4 will serve to illustrate this.
________________________________________________________________
(deceleration Time )
key
key
key 3 times; then the
key to save.
PRGM
key to return to the main display.
DRIVE
Resulting Display
Bn-02
Dec. Time 1
Bn-02 = 0010.0 s
Dec. Time 1
Bn-02 = 0030.0 s
key twice
Dec. Time 1
Entry Accepted
Bn-02 = 0030.0 s
Dec. Time 1
TECO – Westinghouse Motor Company
Flashing
Flashing
2 Seconds
Flashing
16