Mitsubishi Electric CITY-MULTI PAC-PH01EHY-E Installation Manual page 35

Air-conditioners for building application, outdoor unit panel heater
Table of Contents

Advertisement

<PAC-PH02EHY-E>
Step 1. Panel heater wiring
• Wiring on the left side and installing the wiring cover
[Fig. 8.1.1.1]
<A> Pull up the panel heater wirings so that the wirings run
along the left rear pillar.
<B> Thread the panel heater wirings through the long hole
on the left rear pillar.
<C> Attach the rubber sheet to the left frame so that the heat
exchanger fin will be covered. (Using the wiring access
hole and the tab on the frame as a reference position)
<D> Pull the wiring through the hole on the left frame and
bring it into the inner side of the heat exchanger.
A Panel heater wiring
B Left rear pillar
C Left frame
D Plate rubber
E Wire seal
* If the frame is not painted, place the supplied wire seal
around the hole.
[Fig. 8.1.1.2]
<A> Screw down the metal sheet wiring cover at three points.
A Cover wiring 1
B Cover wiring 2
C Cover wiring 4
[Fig. 8.1.1.3]
<A> Pull up the panel heater wirings so that the wirings run
along the right rear pillar.
<B> Thread the panel heater wirings through the long hole
on the right rear pillar.
<C> Pull the wirings from the end of the heat exchanger and
bring them into the inner side of the heat exchanger.
A Panel heater wiring
B Right rear pillar
C Right frame
D Heat exchanger fixing plate
E Wire seal
* If the wiring comes in contact with the edges of the heat
exchanger fixing plate, place the supplied wire seal.
[Fig. 8.1.1.4]
<A> Screw down the metal sheet wiring cover at three points.
A Cover wiring 1
B Cover wiring 3
• Wiring on the right and left rear sides and installing the
wiring cover
[Fig. 8.1.1.5]
<A> Pull up the panel heater wirings so that the wirings run
along each pillar.
<B> Thread the panel heater wirings through the long hole
on the right rear pillar.
<C> Run the panel heater wirings between the left rear pillar
and the heat exchanger.
<D> Pull the wirings from the end of the heat exchanger and
bring them into the inner side of the heat exchanger.
<E> Attach the rubber sheet to the left frame so that the heat
exchanger fin will be covered. (Using the wiring access
hole and the tab on the frame as a reference position)
<F> Thread the wirings through the hole on the left frame,
and bring them into the inner side of the heat
exchanger.
A Panel heater wiring
B Right rear pillar
C Left rear pillar
D Right frame
E Left frame
F Plate rubber
G Heat exchanger fixing plate
H Wire seal
*1 If the wiring comes in contact with the edges of the heat
exchanger fixing plate, place the supplied wire seal.
*2 If the frame is not painted, place the supplied wire seal
around the hole.
[Fig. 8.1.1.6]
<A> Screw down the metal sheet wiring covers at three
points.
A Cover wiring 1
B Cover wiring 2
C Cover wiring 3
Step 2. Fastening the panel heater wirings
[Fig. 8.2.1.1]
<A> Fasten the panel heater wirings with the cable strap on
the center front pillar together with the strong electrical
wiring.
<B> When performing <A> above, if the panel heater wirings
are in contact with the heat exchanger, refrigerant
piping, and sheet metal edges, wrap the supplied pipe
cover around the pipe so that the wirings are out of
contact with them. Then, fix the wirings in place with a
cable tie.
<C> Fasten the panel heater wirings with the cable strap for
holding strong electrical wiring on the outside of the
control box together with other wirings.
<D> Thread the panel heater wirings through the cable hole at
the lower part of the control box along with other wirings.
<E> Thread all wirings on the left through the hole below the
control box.
A Center front pillar
B Cable strap for strong electrical wiring (on the center
front pillar)
C Panel heater wirings
D Cable strap for strong electrical wiring (on the outside of
the control box)
35