Electrical Wiring - Mitsubishi Electric CITY-MULTI PAC-PH01EHY-E Installation Manual

Air-conditioners for building application, outdoor unit panel heater
Table of Contents

Advertisement

8. Electrical Wiring

<PAC-PH01EHY-E>
Step 1. Panel heater wiring
• Wiring on the left side and installing the wiring cover
[Fig. 8.1.0.1]
<A> Pull up the panel heater wirings so that the wirings run
along the left rear pillar.
<B> Thread the panel heater wirings through the long hole
on the left rear pillar.
<C> Attach the rubber sheet to the left frame so that the heat
exchanger fin will be covered. (Using the wiring access
hole and the tab on the frame as a reference position)
<D> Pull the wiring through the hole on the left frame and
bring it into the inner side of the heat exchanger.
A Panel heater wiring
B Left rear pillar
C Left frame
D Plate rubber
E Wire seal
* If the frame is not painted, place the supplied wire seal
around the hole.
[Fig. 8.1.0.2]
<A> Screw down the metal sheet wiring cover at three points.
A Cover wiring 1
B Cover wiring 2
C Cover wiring 4
• Wiring on the right side and installing the wiring cover
[Fig. 8.1.0.3]
<A> Pull up the panel heater wirings so that the wirings run
along the right rear pillar.
<B> Thread the wiring through the hole on the right rear
pillar and bring it into the inner side of the heat
exchanger.
A Panel heater wiring
B Right rear pillar
C Right frame
D Heat exchanger fixing plate
E Wire seal
* If the wiring comes in contact with the edges of the heat
exchanger fixing plate, place the supplied wire seal.
[Fig. 8.1.0.4]
<A> Screw down the metal sheet wiring cover at three points.
A Cover wiring 1
B Cover wiring 3
34
• Wiring on the rear side and installing the wiring cover
[Fig. 8.1.0.5]
<A> Pull up the panel heater wirings so that the wirings run
along the right rear pillar.
<B> Thread the wiring through the hole on the right rear
pillar and bring it into the inner side of the heat
exchanger.
A Panel heater wiring
B Right rear pillar
C Right frame
D Heat exchanger fixing plate
E Wire seal
* If the wiring comes in contact with the edges of the heat
exchanger fixing plate, place the supplied wire seal.
[Fig. 8.1.0.6]
<A> Screw down the metal sheet wiring cover at three
points.
A Cover wiring 1
B Cover wiring 2
Step 2. Fastening the panel heater wirings
[Fig. 8.2.0.1]
<A> Run the panel heater wirings outside the unit. Wrap the
supplied pipe cover around the pipe so that the heat
exchanger, refrigerant piping, and sheet metal edges
are out of contact with panel heater wirings located
between the heat exchanger and where indicated as
<A> in the figure. Then fix the pipe cover and the
wirings in place with a cable tie.
<B> Re-place the main control box and the wirings.
A Panel heater wiring
B Main control box
[Fig. 8.2.0.2]
<A> Remove the cover from the inverter control box by
unscrewing the three screws.
A Main control box
B Inverter control box
[Fig. 8.2.0.3]
<A> Run the panel heater wirings along with the strong
electrical wiring in the back of the main control box, and
fasten them with cable straps.
A Strong electrical wiring
B Cable strap
C Panel heater wiring

Advertisement