Setting The Fuel Gas Type (If Band P (Lpg) Is Used); Checking The Date And Time In The Ghp Outdoor Unit - Panasonic GHP Test Run Manual

Hybrid
Table of Contents

Advertisement

Table 2 Name and function of each switch on U-10MES2E8 outdoor unit control P.C.board
Function switch
RC plug (3P, BLU)
(CN73)
AP pin (2P, WHT)
(CN24)
SNOW plug (3P, RED)
(CN34)
SILENT plug (2P, WHT)
(CN33)
OC EMG terminal
(3P, BLK) (CN69)
RC1 EMG terminal
(3P, BLK) (CN82)

3. . Setting the Fuel Gas Type (If Band P (LPG) is Used)

* When using Band P (LPG) for fuel gas, the gas type has to be configured.
* The outdoor unit power breaker remains OFF.
(1) Move the lever of the N/P switch that is attached to the mixer part of the engine to the position shown in the diagram.
Turn it 180 degrees in the anticlockwise direction (there is a stopper provided). Do not apply unnecessary force to turn it
any further.
CAUTION
(2) Mount the attached short-circuit connector to the
N/P switch (Fig. 1) of the outdoor control board.
* Switch on the power breaker of the outdoor unit.
(3) Apply the < Gas type set and adjusted > label in the PL NAME designated location in the electrical box.
(4) After making the setting, use an ink pen or other tool to make a mark so that the original setting position of the lever is
known.

4. . Checking the Date and Time in the GHP outdoor unit

 Checking
(1) Select the
Example:
(2) With the date displayed, press the SET key to switch to the time display.
Example:
(3) With the time displayed, press the SET key to switch back to the date display.
* If the curre t date and time display are not correct, reset (correct) them.
 Setting (correcting)
(1) With the date or time displayed, press and hold the SET key for 1 second to enter setting mode.
Example:
(2) Each time the SET key is pressed, the setting contents are confirmed and the first digit display changes. The settings
are as shown in Table 3. After
Connects to outdoor unit maintenance remote controller and content of alarm message will be
checked.
Can be used when vacuuming the outdoor unit.
Can be used when installing a snowfall sensor device.
Can be used when setting the outdoor unit fan in sound absorbing mode.
If "TO INDOOR UNIT" accidently connected to high voltage, use the terminal base TM1.
Method: 1. Replace the pins 1 and 2 of CN69 with the pins 2 and 3.
2. . Disconnect J
1.
If "TO OUTDOOR UNIT" accidently connected to high voltage, use the terminal base TM1.
Method: 1. Replace the pins 1 and 2 of CN82 with the pins 2 and 3.
2.
. Disconnect JP1
After installing, be sure to
check that there is no gas
leakage. There is the danger
of fire if gas leaks
(date display) menu item to display the current date.
(April 1, 2018)
(11 h 05 m 25 s)
(2018)
is displayed for the first digit, the display returns to
Remarks
Lever
When shipping
Ⅱ-6
Lever
When the Band P (LPG) is setting
Fig. 3
.