Download Print this page

Kutai electronics EA321 Operation Manual

Generator automatic voltage regulator use with pmg brushless generators compatible with newage mx321

Advertisement

Quick Links

EA321
Generator Automatic Voltage Regulator
Operation Manual
Use with PMG brushless generators
Compatible with Newage MX321*
* All manufacturer names and numbers are used for reference purpose only
and do not imply that any part is the product of these manufacturer.
KUTAI ELECTRONICS INDUSTRY CO., LTD.
TEL : +886-7-8121771
FAX : +886-7-8121775
Website : www.kutai.com.tw
Headquarters : No.3, Ln. 201, Qianfu St., Qianzhen Dist., Kaohsiung City 80664, Taiwan

Advertisement

loading

Summary of Contents for Kutai electronics EA321

  • Page 1 Compatible with Newage MX321* * All manufacturer names and numbers are used for reference purpose only and do not imply that any part is the product of these manufacturer. KUTAI ELECTRONICS INDUSTRY CO., LTD. TEL : +886-7-8121771 FAX : +886-7-8121775 Website : www.kutai.com.tw...
  • Page 2: Section 1 : Specification

    Max.18 watts Vibration Quadrature Droop Input Dimensions Burden 10 ohms 203.5 (L) x 153.6 (W) x 43.5 (H) mm Max. input 0.33 A Max. sensitivity 0.22 A for 5% droop (PF = 0) Weight 530 g +/- 2% ___________________________________________________________________________________________ EA321...
  • Page 3: Section 2 : General Description

    SECTION 2 : GENERAL DESCRIPTION Provision is made for the connection of a remote voltage trimmer, allowing the user fine control of EA321 is a three phase sensed Automatic the generator’s output. Voltage Regulator and forms part of the excitation system for a brush-less generator.
  • Page 4: Section 4 : Adjustment Of Avr Controls

    KW rating of the a controller. generator. The correct setting of the Stability adjustment can be found by running the generator at no load and slowly turning the stability control anti-clockwise until the generator ___________________________________________________________________________________________ EA321...
  • Page 5: Section 5 : Fitting And Operating

    DROOP VOLTS unstable under with changes in load. Avoid making I/LIMIT TRIM any changes to the U/F setting unless necessary. 5. Set the O/E potemtiometer at max. position when paralleling. Figure 1 Outline Drawing ___________________________________________________________________________________________ EA321...
  • Page 6 Volts Ramp No link 6P50HZ 6P60HZ I Limit 4P50HZ 4P60HZ UFRO Frequency Selection Indicator EA321 Dwell Stability >550KW 90-550KW <90KW Stability Selection Droop Over V Exc. B0 B1 Trim Figure 2 Disposition Drawing 3 Bridge Exciter 220V Generator E0 E1...