4. Good connectivity can also be achieved in other orientations. The
antenna should also be approximately 1 m (3 ft.) from any large
structure, building, or conductive surface, and a minimum of 2m (6
ft.) and a max of 4m (13 ft.) from the ground to allow for clear
communication to other devices.
4.6
Mounting
Procedure
1. Locate the Location Anchor on a vertical or horizontal structure. Align
the Location Anchor as shown in
2. Tighten clamp to 10.2 N-m (90 in-lb).
3. If commissioning the Location Anchor, remove the electronics cover,
move the power switch to the on position.
4. Ensure the cover is fully tightened to prevent moisture ingress. The
lip of the polymer electronics cover should be in contact with the
surface of the polymer enclosure to ensure a proper seal. Do not
overtighten.
Figure 4-1: Location Anchor Mounting
Quick Start Guide
Figure
4-1.
Quick Start Guide