BURNER ADJUSTMENT TABLE

NON-RETROFIT APPLICATIONS
If this burner is being installed in a packaged unit (i.e. Burner comes with a boiler or furnace), follow the instal-
lation and set-up instructions supplied with the heating appliance, as settings will differ from those shown in
this manual.
Weil McLain Part No.
Riello Part No.
Burner Model
Input
Nozzle
Pump Pressure
Turbolator Setting
Air Gate Setting
Air tube length
Ait tube insertion
*1 Nozzle pre-installed at factory.
NOTE:
The above set up charts are a starting point only.
The burner and appliance must be properly set up using proper combustion testing equipment.
Note: Any approved oil burner nozzle type, angle and manufacturer maybe used, as long as input is corresponding the
correct BTU/hr. or US gph input rating of the appliance.
COMBUSTION CHAMBER
Follow the instructions furnished by the boiler/furnace manufacturer. Size retrofit application according to the appropri-
ate installation codes (e.g. CSA B139 or NFPA #31).

BURNER START-UP CYCLE

Normal
Thermostat
Motor
Ignition transformer
Valve
Flame
Lock-out lamp
3223
RIELLO BURNER SET UP SHEET
Riello 40
F5
Series
Boiler
UO3
GPH
0,8
Delavan
.65 X 70°B
PSI
150
0
2.75
inches
8
inches
4 1/4"
~ 12s
8000-5700
8000-5800
C8512519
C8512520
F5 Factory
F5 Factory
preset *1
preset *1
UO3
1,0
.85 X 60°B
1.00 X 70°B
145
1
2.8
8
4 1/4"
Lock-out, due to light-failure
~ 12s
8000-5900
C8512521
F5 Factory
preset *1
UO4
UO5
1,2
1,4
1.10 X 70°B
145
160
3
4
2.9
2.9
8
8
4 1/4"
4 1/4"
~ 5s
GB
D5229
12