CONFIGURATION BY PC
By software DATESOFT it is possible to:
- set the default programming of the device;
- program the options not available with the dip-switch;
(burn-out level, etc...);
- read, in real time, the input and output measures;
- follow the dip-switches configuration wizard.
To configure the device follow the next steps:
1) Power-on the device.
2) Open the protection plastic label on the front of the device.
3) Connect the interface PRODAT to the PC (COM port)
and to the device (PGRM connector).
4) Open DATESOFT.
5) Select the COM port in use.
6) Click on "Open COM".
7) Click on "Program".
8) Set the programming data.
9) Click on "Write" to send the programming data to the device.
Warning: during these operations the device must always be powered and the TX/RX cable always connected.
For information about DATESOFT refer to the software's user guide.
CONFIGURATION BY DIP-SWITCHES
Output
Full scale
1
2
3
4
5
6
7
8
SW2
1
2
3
4
5
6
7
8
SW1
Input type
Zero
NOTE:
- It is also possible to set the dip-switches using the wizard of the configuration software following the procedure described in the section "Configuration by
PC" until the step 6 and clicking on "Switch".
DIP-SWITCH CONFIGURATION TABLES
TAB.1
Input type settings
SW1
SW1
1
2
3
4
1
2
3
EPROM *
R 2KΩ
R 500Ω
Pt100
Ni100
Pt1000
Ni1000
---
TAB.2
Output settings
SW2
4
7
8
---
0-20 mA
---
4-20 mA
---
0-10 V
---
0-5 V
---
---
---
---
PROGRAMMING
POWER SUPPLY
UNIT
V+ V-
Q
DAT
1) Open the suitable door on the side of the device.
2) Set the input type by the dip-switch SW1 [1..4] (see TAB.1)
3) Set the minimum input scale value (Zero) by the dip-switch SW1 [5..8] (see TAB.3)
4) Set the maximum input value (Full scale) by the dip-switch SW2 [1..6] (see TAB.3)
5) Set the output type by the dip-switch SW2 [7..8] (see TAB.2)
EX. of configuration:
- Input type
- Zero value
OFF
- Full scale value
ON
- Output type
NOTES:
* For all the input type selected by dip-switches, the compensation of wires is
fixed at 3.
* To configure the range for the input type selected (TAB.1) refer to the section
of the TAB.3 on next page relative to it (ex: for Pt100 use the table TAB.3c ).
* If the dip-switches SW1 [1..4] are all set in the position 0 ("EPROM"), the
device will follow the configuration programmed by PC ( input type and range,
output type and range and options).
* If the dip-switches SW1 [5..8] are all set in the position 0 ("Default"), the
device will follow the input scale programmed by PC for the input type
selected by the dip-switches SW1 [1..4]
* Eventual wrong dip-switches settings will be signalled by the blinking of the
led "PWR".
PRODAT
TX/RX CABLE
Plastic label protection
R
PGRM
SW1 =
Pt100
-50 °C
SW2 =
200 °C
4-20 mA
COM PORT
P.C.