Download Print this page

Datexel DAT 4532 C General Description

Isolated, double channel converter for ptc/ntc/pot configurable by dip-switch or pc

Advertisement

Quick Links

Via monte Nero, 40/B – 21049 TRADATE (VA) ITALY
Phone: +39 (0)331841070 Fax:+39 (0)331841950 -
FEATURES
- Configurable input for PTC, NTC and Pot.
- Configurable output in current or voltage
- Double channel in the same enclosure
- Configurable by dip-switch or PC
- High accuracy
- On-field reconfigurable
- Galvanic isolation among the ways
- EMC compliant – CE mark
- Suitable for DIN rail mounting in compliance
with EN-50022 and EN-50035
GENERAL DESCRIPTION
The isolated double channel converter DAT 4532 C is able to measure and linearise the standard PTC and NTC sensors and potentiometers. In function
of programming, the measured values are converted in a current or voltage signal. The device guarantees high accuracy and performances stability both
versus time and temperature.
The double channel allows the high density mounting where is necessary to reduce the encumbrances.
The programming is made by the dip-switch located in the window on the side of the enclosure. By means of dip-switches it is possible to select the input
type and range and the output type without recalibrate the device.
Moreover, by Personal Computer the user can program all of the device's parameters for his own necessity; the configuration by PC allows to program
the two channels with two independent settings.
Moreover it is available the option of alarm for signal interruption (burn-out) that allows to set the output value as high or low out of scale .
The 1500 Vac galvanic isolation on all ways (inputs, outputs and power supply) eliminates the effects of all ground loops eventually existing and allows
the use of the converter in heavy environmental conditions found in industrial applications.
The DAT 4532 C is in compliance with the Directive 2004/108/EC on the Electromagnetic Compatibility.
It is housed in a plastic enclosure of 12.5 mm thickness suitable for DIN rail mounting in compliance with EN-50022 and EN-50035 standards.
USER INSTRUCTIONS
The converter must be powered by a direct voltage applied to the terminals Q and R.
The channel A measures the value from the sensor connected to the terminals I, L and G and transmits the output measure on the terminals N and M.
The channel B measures the value from the sensor connected to the terminals E, F and H and transmits the output measure on the terminals P and O.
The input and output connections must be made as shown in the section "Connections".
It is possible to configure the converter on field by dip-switch or Personal Computer as shown in the section " Programming ". The configuration by
dip-switches can be made also if the device is powered (note: after the configuration the device takes some seconds to provide the right output measure ).
INPUT (2 channels)
Input type
Min
PTC
KTY81-210
-55°C
KTY81-220
-55°C
KTY84-130
-40°C
KTY84-150
-40°C
NTC
Coster 10K
-10°C
Coster 1K
-30°C
0 %
Pot.
(Rnom.< 50KΩ)
Input Calibration
(1)
PTC, NTC
the higher of ±0.1% and ±0.2°C
Potentiometer
± 0.05 % f.s.
Linearity
(1)
PTC, NTC
± 0.1 % f.s.
Sensor excitation current
PTC, NTC
500 uA
Thermal drift
(1)
Full scale
± 0.01% / °C
(1)referred to the input Span (difference between max. and min.)
e-mail:datexel@datexel.it
TECHNICAL SPECIFICATIONS (Typical at 25 °C and in nominal conditions)
OUTPUT(2 channels)
Max
Min.Span
Output type
Current
150°C
50°C
Voltage
150°C
50°C
300°C
50°C
Output calibration
300°C
50°C
Current
Voltage
100°C
50°C
Burn-out values
40°C
25°C
Max. output value
100 %
10 %
Min. output value
Output load Resistance - Rload
Current output
Voltage output
Short circuit current
Response time
-
www.datexel.it
INPUT A
OUTPUT A
NTC
PTC Pot
V
INPUT B
OUTPUT B
NTC
PTC Pot
V
DC SUPPLY
+
-
Min
Max
Min Span
0 mA
20 mA
4 mA
0 V
10 V
1 V
± 7 uA
± 5 mV
22 mA or 10.6 V
0 mA or -0.6 V
< 500 Ω
> 10 KΩ
26 mA max.
500 ms
(10÷ 90%)
about
Isolated, double channel
converter for PTC/NTC/Pot
configurable by Dip-Switch or PC
DAT 4532 C
DAT 4532 C
mA
mA
POWER SUPPLY
Power supply voltage
Reverse polarity protection
Current consumption
Current output
Voltage output
ISOLATION
Among all ways
TEMPERATURE AND HUMIDITY
Operative temperature
Storage temperature
Humidity (not condensed)
HOUSING
Material
Self-extinguishing plastic
Mounting
DIN rail in compliance
with EN-50022 and
EN-50035
Weight
about 90 g.
EMC ( for industrial environments )
Immunity
Emission
18 .. 30 Vdc
60 Vdc max
55 mA max.
25 mA max.
1500 Vac,
50 Hz, 1 min
-20°C .. +60°C
-40°C.. +85°C
0 .. 90 %
EN 61000-6-2
EN 61000-6-4

Advertisement

loading

Summary of Contents for Datexel DAT 4532 C

  • Page 1 GENERAL DESCRIPTION The isolated double channel converter DAT 4532 C is able to measure and linearise the standard PTC and NTC sensors and potentiometers. In function of programming, the measured values are converted in a current or voltage signal. The device guarantees high accuracy and performances stability both versus time and temperature.
  • Page 2 PROGRAMMING CONFIGURATION BY PC PRODAT By software DATESOFT it is possible to: - set the default programming of the device; POWER SUPPLY - program the options not available with the dip-switch; UNIT (burn-out level, etc...); - read, in real time, the input and output measures; V+ V- - follow the dip-switches configuration wizard.
  • Page 3 TAB.3a – Settings for PTC, NTC Zero Full scale °C °C °C °C °C Default Default -200 -150 -100 TAB.3b –Settings for Potentiometer Zero Full scale Default Default...
  • Page 4 DAT 4532C / KTY84-130 / 0 ÷ 200 °C / 4 ÷ 20 mA Input type Input range Output range ED.03.08-R.06 Datexel reserves its rights to modify totally or in part the characteristics of its products without notice at any time...