Fiber-Optic Connections, Tx, Rx - Siemens 7XV5450-0BA00/DD Manual

Accessories mini star coupler, version /dd and higher
Table of Contents

Advertisement

Available languages

Available languages

NOTE
i
i
The RS232 interface is only active when pin 7 and pin 8 are shorted together using a jumper.
Assignment of the 7XV5100-4 RS232 Cable
The RS232 cable is used to connect the serial 9-pin PC port (for example COM1) to a protection device, optical
mini star coupler, or converter with a 9-pin user interface.
[dw_pin assignment7XV5100-4, 1, en_US]
Figure 2-4
NOTE
i
i
Siemens recommends grounding the shield of the RS232 cable.
2.2.2.3

Fiber-Optic Connections, Tx, Rx

NOTE
i
i
Use only optical fibers prepared as per regulations.
You can order a fiber-optic cable from Siemens with the order numbers 6XV8100 or 6XV8200.
Connect the fiber-optic cable via the ST connectors with the appropriate fiber-optic elements.
NOTE
i
i
When routing fiber-optic cables, pay attention to the prescribed bending radius.
NOTE
i
i
After connecting to the device, tighten the screws on the D-sub plug connector.
Accessories, Mini Star Coupler, Manual
C53000-G9050-C595-1, Edition 05.2020
Pin Assignment 7XV5100-4
Device Structure
2.2 Device Connections
19

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

7xv5450-0ba00/bb7xv5450-0ba00/cc