Effective December 2010
Table 12. Cause-of-Status Code Definitions
Code
Definition
0
Unknown
1
Normal operating mode
3
Instantaneous phase overcurrent
11
Overvoltage
12
Undervoltage
15
Underfrequency
16
Overfrequency
17
Current unbalance
18
Voltage unbalance
19
Apparent power factor
26
Power demand
27
VA demand
30
Total harmonic distortion
31
Operations count
33
Control via communications
37
Coil supervision
39
RAM error
43
EEROM error
46
Watchdog
61
Long delay phase overcurrent
62
Short delay phase overcurrent
63
Fixed instantaneous phase
overcurrent #1
64
Bad/missing rating plug
Code
Definition
65
Reverse power
66
Fixed instantaneous phase overcurrent #2
67
Reverse phase
68
Reverse sequence
69
Phase current loss
71
Alarm active
72
Bad frame
73
Phase currents near pickup
75
Making current release
76
Fixed instantaneous phase overcurrent #3
77
Set points error
78
Over-temperature
80
Long delay neutral overcurrent
82
Historical data
84
Ground fault (instantaneous or delay)
85
Earth fault (instantaneous or delay)
146
Frequency out of range
148
Check auxiliary switch
149
Overcurrent
153
Maintenance mode
154
Breaker mech. fault
156
Disconnect position
157
Trip Actuator
Instructional Leaflet IL01301034E

Section 8: Troubleshooting

The following are the most common issues experienced
with the installation of a Series NRX Modbus communica-
tions adapter module. If you have additional questions or
need further information and/or instructions, please contact
your local Eaton representative or visit www.eaton.com.
Observation 1—Status LED not flashing
Action—Verify proper input power to module connectors.
Observation 2—Status LED flashing green, but module
does not change state in response to master command
requests
Action—Verify correct module address.
Action—Verify communication cable
is connected correctly from master
to module.