6.6 Troubleshooting Outdoor Error
Sensor Checking Methods
Checking single units of sensors
Purpose
Compressor discharge sensor
- Position : Outlet of compressor
- Sensor value : 200kΩ ± 10%
(Based on 25℃)
200
Ω
Outdoor temperature sensor
Copyright ©2014 LG Electronics. Inc. All right reserved.
Only for training and service purposes
for fault
Compressor
inlet sensor
Items for checking Measurement of the unique resistance by
sensor temperature.
Pipe sensor
- Position : Compressor inlet and pipe
- Sensor value : 5kΩ ± 10%
(Based on 25℃)
5
Ω
- Position : Rear part of outdoor device
- Sensor value : 10kΩ ± 10%
(Based on 25℃)
- 78 -
Part 4 Trouble Shooting
Pipe sensor
5
Ω
10
Ω
LGE Internal Use Only