LG ABNW85GB9A0 Svc Manual page 44

Hide thumbs Also See for ABNW85GB9A0:
Table of Contents

Advertisement

6.5 Troubleshooting Indoor Error
CH 10 (Indoor unit BLDC fan motor failure)
Is connector
connection proper?
Yes
Is fan motor
normal?*
Yes
Replace indoor unit PCB **
* It is normal when check hall sensor of indoor fan motor as shown below
1
4 5 6 7
<Checking connection state of fan motor connector>
** Replace the indoor unit PCB, and then make sure to do Auto addressing and input the
address of central control
(Notice: The connection of motor connector to PCB should be done under no power
supplying to PCB)
Copyright ©2014 LG Electronics. Inc. All right reserved.
Only for training and service purposes
No
Connect properly
No
Replace indoor unit fan motor
Each termainl with the tester
Tester
+
-
1
4
5
4
6
4
7
4
Normal resistance(±10%)
TH chassis
TD chassis
k
hundreds kΩ hundreds kΩ
hundreds kΩ hundreds kΩ
- 44 -
Part 4 Trouble Shooting
LGE Internal Use Only

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents