ROTARY SWITCH SETTING

32
ROTARY SWITCH SETTING
Rotary switch setting
According to the type of the heat source applied to AHU, set the rotary switch.
CONTROL KIT inside
Rotary switch
Rotary switch
Rotary switch
(AHU Controller)
h If the cycle is composed by connecting 'cooling only outdoor unit + heating separately heat
source (hot water /steam /electricity)', set the rotary switch to No. 2.
Dip switch setting according to AHU Type and whether sensor is applied
CONTROL KIT inside
Rotary switch
Rotary switch
Rotary switch
(AHU Controller)
Rotary switch setting
Factory ship-out state
Applied heat source
Rotary
Possible operation
switch
Cooling Heating
Cooling/heating/dehu-
Air
Air
0
cooled
cooled
midification/power
type
type
saving/wind only
Cooling/dehumidifica-
Air
5
cooled
-
tion/power
type
saving/wind only
Cooling/heating/
Water
Water
7
cooled
cooled
dehumidification/
type
type
power saving/wind only
F
-
-
wind only
Dip switch(Factory ship-out state)
Dip switch
State
No. 1~23
OFF
No.24
ON
Outdoor unit
mode
Heat pump
Cooling only
Heat pump
-

Hide quick links: