more detailed error messages available under the menu item " Diagnostics" via
the respective adjustment module.
Status messages
The status messages are divided into the following categories:
and explained by pictographs:
1
2
3
4
Figure 10.1
Failure: Due to a malfunction in the transmitter, a fault message is output.
This status message is always active. It cannot be deactivated by the user.
Function check: The transmitter is being worked on, the measured value is
temporarily invalid (for example during simulation).
This status message is inactive by default.
Out of specification: The measured value is unreliable because an transmitter
specification was exceeded (e.g. electronics temperature).
This status message is inactive by default.
Maintenance required: Due to external influences, the transmitter function is
limited. The measurement is affected, but the measured value is still valid. Plan in
maintenance for the transmitter because a failure is expected in the near future (e.g.
due to buildup).
This status message is inactive by default.
Failure
Code
Text message
F013
SITRANS LR110
Operating Instructions, 08/2020, A5E49829006
Failure
Function check
Out of specification
Maintenance required
Failure - red
Out of specification - yellow
Function check - orange
Maintenance required - blue
Pictographs of the status messages
Cause
No measured value in the
switch-on phase or during
operation
Diagnostics and troubleshooting
10.4 Status messages according to NE 107
Rectification
Check or correct installation
and/or parameter settings
DevSpec
State in CMD 48
Byte 5, Bit 0 of
Byte 0 ... 5
35