Installing/mounting
4.3 Mounting instructions
Figure 4.6
Nozzle diameter d
40 mm
50 mm
80 mm
100 mm
150 mm
Orientation
In liquids, direct the device as perpendicular as possible to the medium surface to
achieve optimum measurement results.
Figure 4.7
Agitators
If there are agitators in the vessel, an auto false echo suppression should be
carried out with the agitators in motion. This ensures that the interfering
reflections from the agitators are saved with the blades in different positions.
16
Nozzle mounting with deviating nozzle dimensions
1½"
2"
3"
4"
6"
Alignment in liquids
Nozzle length h
≤ 150 mm
≤ 200 mm
≤ 300 mm
≤ 400 mm
≤ 600 mm
Operating Instructions, 08/2020, A5E49829006
≤ 5.9 in
≤ 7.9 in
≤ 11.8 in
≤ 15.8 in
≤ 23.6 in