Combustion
In case the combustion values found at the beginning of the inter-
vention do not respect the standards in force or, in any case, do
not correspond to a proper combustion, contact the Technical
Assistant and have him carry out the necessary adjustments.
Allow the burner to work for 10 min. and then check the
combustion readings with the parameters indicated within the
9.3

Opening the burner

Disconnect the electrical supply from the burner
by means of the main system switch.
DANGER
Turn off the fuel interception tap.
DANGER
Wait for the components in contact with heat
sources to cool down completely.
After carrying out maintenance, cleaning or
checking operations, reassemble the hood and all
the safety and protection devices of the burner.
Maintenance
appliance instruction manual. Then carry out a combustion
check verifying:
– Smoke temperature at the chimney;
– Content of CO
– Content of CO (ppm);
– Smoke value according to opacity smokes index according to
Bacharach scale.
29