Vermont Castings 1990 Installation And Operating Manual page 17

Woodburning stove
Table of Contents

Advertisement

Distance from the Center of the Flue Collar to the Wall in Top-Exit Installations
The information on this page is helpful in planning stove placement for top-exiting installations, particularly those in-
stallations with chimneys that pass through the ceiling. However, this is not a clearance chart. Final stove clearances
must adhere to the guidelines stated in the clearance charts on Page 14.
Intrepid II: WITHOUT Stove and Chimney Connector Heat Shields
Unprotected Surfaces
Parallel Installations
Side (A)
34³⁄₄"
(883 mm)
A
*
* This distance, from the center of the flue collar to the front edge of the hearth, is the same for all installations on this page: 31" in the United
States and 33" (840mm) in Canada.
Intrepid II: WITH Stove and Chimney Connector Heat Shields
Unprotected Surfaces
Parallel Installations
Side (A)
34³⁄₄"
(883 mm)
A
** To locate center of flue collar for corner installation, add 7" (180mm) to the clearance distance form stove corner to wall. Mark off the resulting
distance from the corner along both walls. Next, measure the same distance form these two points out from the walls. These last two measure-
ments will meet at a point representing the center of the flue collar. Refer to the diagrams above.
2000966
Corner
Installations**
Rear (B)
Corner (C)
29"
26³⁄₄"
(737 mm)
(680 mm)
B
C
ST51
Intrepid
Corner
flue centerline
Installations**
Diagrams
Rear (B)
Corner (C)
11/16/00
15"
18³⁄₄"
(381 mm)
(476 mm)
B
C
ST511a
Intrepid
flue centerline
Diagrams
11/16/00
Parallel Installations
Side (D)
22³⁄₄"
(578 mm)
D
*
Parallel Installations
Side (D)
22³⁄₄"
(578 mm)
D
Intrepid II Woodburning Stove
Protected Surfaces
Rear (E)
11"
(279 mm)
E
Protected Surfaces
Rear (E)
8"
(203 mm)
E
Corner
Installations**
Corner (F)
16³⁄₄"
(426 mm)
F
ST511
Corner
Installations**
Corner (F)
16³⁄₄"
(426 mm)
F
ST511a
17