eControls T200WLD User& Installer's Manual page 8

Direct damper control
Table of Contents

Advertisement

2) Damper Wiring (Continued)
Solid green LED indicates open damper position.
Solid red LED indicates closed damper position.
Green and red LEDs blinking indicates damper is in a
modulated position.
Power Failure - When power is restored, the damper will
go to a fully open position and resume communication
with the Remote Control.
The Remote Control will automatically refresh the
position of the dampers every 15 minutes to the last set
airflow provided the Remote Control is powered and
within 125' of the damper.
3) Testing Communication
Use the steps below to test the installation to insure the
dampers are wired and set properly.
1.
Turn power On to the actuator and observe the dampers go
to the fully open position and the Green LED turns On.
2.
Press the System key to display Heat. Press the Down
key until the setpoint temperature is several degrees lower
than the Inside Temperature. The damper goes to the
closed position and the Red LED is On.
3.
Press the Up key until the setpoint temperature is several
degrees higher than the Inside Temperature. The damper
goes to the fully open position indicated by the Green LED
on or a modulated position indicated by the Green and Red
LEDs blinking.
Changing the Damper Zone Number
The dampers are factory set for Zone1 and Address 1 and only
need to be changed when more than one thermostat is used in
an installation.
1.
Press and hold the pushbutton
switch and the green LED blinks
once, pauses and blinks twice,
pauses and blinks three times, etc.
Release the switch after the
number of blinks corresponding to
the Zone number to be set.
The zone number can be reset at
any time.
Limited 5-Year Warranty
The 5-year warranty is limited to the repair or replacement of
defective product due to parts failure or defective workmanship.
Push button
switch
Green LED
Changing the Damper Home Address
The dampers are factory set for Address 1 and only need to be
changed when two or more installations are within 300' of one
another.
1.
Turn power Off to the actuator.
2.
Press and hold the pushbutton
switch while applying 24VAC power
to the actuator. The red LED blinks
once, pauses and blinks twice,
pauses and blinks three times, etc.
Release the switch after the
number of blinks corresponding to
the Address to be set.
The Address number can be reset
at any time.
Setting Bypass
The R80DWL Damper actuator has a Close position limit that
can be used to insure minimum airflow even when the damper
has been set to 0% Airflow. The minimum Close Position can
be set from about 50% closed to fully closed.
Set Screw
Set Screw
Close Cam
Close Cam
Set the damper to the fully open position by applying 24VAC to
24VAC terminals.
Loosen the set screw and rotate the Close Cam clockwise and
gently tighten the set screw. With the cam set in the fully
counter clockwise position, the damper will completely close.
In the fully clockwise position, the damper will close to about
50% closed allowing some air to pass even when the user sets
the damper to fully closed. Replace the cam cover.
26072 Merit Circle #110 / Laguna Hills, CA 92653
Push button
switch
Red LED
Cam Cover
Cam Cover
eControls
eControls
949-916-0945 Fax 949-458-8502
www.eControlsUSA.com