INSTALLING THE NEUTRAL COMPONENTS
10. Reference Figure 7
If branch neutral terminal strips (Item 18) are
NOT already installed -- or are full -- then the
branch neutral terminal strip (included) must
be installed. Depending upon the feed location,
the branch neutral can be mounted near the
bottom of the Z-rails -- or mirrored to the top --
on a branch neutral connector. Panelboards
should have one mounted already. On Switch-
boards, mount the branch neutral connector
(Item 17) on the neutral bus using (2) 1/4"-20
screws (Item 15). Mount the neutral terminal
strip (Item 18) on either side of the branch
neutral connector using (2) #8-32 screws
(Item 16). Torque all hardware as follows:
For 1/4"-20 screws, refer to torque on label.
For #8-32 screws, torque to 35 lb-in.
INSTALLING COVER PLATE AND FILLERS
11. Reassemble the deadfront assembly to the
interior (removed in Step 3).
12. Reference Figure 8
Install the 3.75" cover plate (Item 7) by aligning
it over the 3.75" of selected unit space and
related breakers. Use a 1/4"-20 x 3/8" screw
(Item 14) on each side of the cover plate and
drive into the deadfront rails. Torque all hardware
as specified on the rear of the deadfront. Mark
the circuit ID cards (Item 8) as desired and
mount them to the cover plate by placing each
behind a clear card holder (Item 9) and pushing
the two into the proper pair of holes in the cover
plate next to the proper circuit. Repeat for each
location. Finally, use blank fillers (Item 10) at
every location that doesn't have a breaker
penetrating through the cover plate.
NOTE: Other cover plates may be required for
proper fit. See filler plate kits listed on the rear
of the deadfront.
COMPLETING THE INSTALLATION
13. Ensure that any bus or breaker hardware is
torqued as specified on the rear of the deadfront.
Then replace all the cover plates and gutter
covers. Finally, ensure any fillers are in place
BEFORE re-energizing the equipment.
These instructions do not purport to cover all details or variations in equipment, or to provide for every possible
contingency to be met in connection with installation, operation or maintenance. Should further information be
desired or should particular problems arise, which are not covered sufficiently for the purchaser's purposes, the
matter should be referred to the local Siemens sales office. The contents of this instruction manual shall not
become part of or modify any prior or existing agreement, commitment or relationship. The sales contract
contains the entire obligation of Siemens. The warranty contained in the contract between the parties is the sole
warranty of Siemens. Any statements contained herein do not create new warranties or modify the existing warranty.
Trademarks - Unless otherwise noted, all names identified by ® are registered trademarks of Siemens AG or
Siemens Industry, Inc. The remaining trademarks in this publication may be trademarks whose use by third
parties for their own purposes could violate the rights of the owner.
WARNING: Do NOT use with NGB, LGB or HGB breakers. ONLY use with NGB2, LGB2 or HGB2 breakers.
PANELBOARD
REFERENCE
Figure 7
SWITCHBOARD
REFERENCE
(to
deadfront
rail)
14
7
Figure 8
8
9
10
-4-
s
SGB2 / SGB2D
Power Panel / Switchboard Kit
for Branch Mounting
Type GB2 Breakers
WARNING: Do NOT use with NGB, LGB or HGB breakers. ONLY use with NGB2, LGB2 or HGB2 breakers.
Installation
Instructions
12-A-1031-01 Rev. 00

Advertisement

loading

Summary of Contents for Siemens SGB2

  • Page 1 Siemens sales office. The contents of this instruction manual shall not become part of or modify any prior or existing agreement, commitment or relationship. The sales contract contains the entire obligation of Siemens.
  • Page 2 7. Reference Figure 4 9. Reference Figure 6 The following instructions are for the installation of Siemens Type GB2 breakers (NGB2, HGB2 or LGB2) as Locate a 0.228” diameter hole in the left Z-rail Align the bottom of the Type GB2 Breaker with the branch devices in a Switchboard or Type P4 or Type P5 Panelboard.