Connections
X20 – 230/115 VAC Power
This connection is used for device variants for 230/115 VAC.
Supply
All internally required voltages are generated by the 230/115 VAC power
supply unit.
CAUTION
The 230/115 VAC connection occurs via a 3-pin inlet connector for non-
heating apparatus on the connector panel. The maximum cable cross
section for the connected cables is 1.5 mm
Fig. 7-15:
Pin assignment of the 230/115 VAC connection X20
Parameters
Rated voltage
Power consumption for U
Power consumption for U
Inrush current for U
Inrush current for U
Line-side fuse

Fig. 7-16: Technical data 230/115 VAC connection

The supply voltage must comply with
overvoltage category II! Otherwise the
integrated power supply unit might be
destructed.
Use an isolating transformer to generate the
230/115 VAC (see following page).
X20
PE
Value
85 VAC ... 264 VAC auto range
= 230 VAC
0.7 A
N
= 115 VAC
1.4 A
N
30 A cold start 25 °C
= 230 VAC
N
15 A cold start 25 °C
= 115 VAC
N
1.6 A (5x20)
IPC 40.2
2
.
Assignment
N1
PE
U2
230V_Buchse.cdr