Ground your system using a copper ground conductor.
Clean and coat all bare grounding connection points on your system with an anti-oxidant
solution before making connections.
Bring all unplated surfaces on your system to a bright finish and treat them with an anti-
oxidant solution before making connections.
Remove any non-conductive surfaces on your system from the threads and connection
points to ensure electrical continuity.
Use the two-hole, Listed, compression-type lug with an AWG 14 gauge wire that uses 4-
in/lb to secure your system to the frame.
NOTE:
The S4048T-ON can operate at -40.5 to -60 VDC at a maximum current level
of 24A or at 100–240 VAC at a maximum current level of 7.1A.
NOTE:
The S4048T-ON is Earthquake Z4-compliant when you attach the
ReadyRails to the frame using threaded hardware. Do not use the tool-less or two-
post installation methods.
NEBS compliance