Function

The unit displays the current system pressure.
It generates output signals according to the operating mode and the parameter setting.
It moreover provides the process data via IO-Link.
The unit is laid out for fully bidirectional communication. So, the following options are possible:
o Remote display: reading and display of the current system pressure.
o Remote parameter setting: reading and changing the current parameter setting.

4.1 Communication, parameter setting, evaluation

OUT1 (Pin 4)
OUT2 (Pin 2)

4.2 Switching function

OUTx changes its switching state if it is above or below the set switching limits (SP1, rP1). The
following switching functions can be selected:
Hysteresis function / normally open: [ou1] = [Hno] (→ fig. 1)
Hysteresis function / normally closed: [ou1] = [Hnc] (→ fig. 1)
First the set point (SP1) is set, then the reset point (rP1). The hysteresis defined remains even if
SPx is changed again.
Window function / normally open: [ou1] = [Fno] (→ fig. 2).
Window function / normally closed: [ou1] = [Fnc] (→ fig. 2).
The width of the window can be set by means of the difference between FH1 and FL1. FH1 =
upper value, FL1 = lower value.
P
SP
rP
1
0
1
0
P = system pressure; HY = hysteresis; FE = window
6
Switching signal for system pressure limit value
Communication via IO-Link
Analog signal 4 ... 20mA / 0 ... 10V
1
FH
HY
FL
t
Hno
Hnc
Electronic Pressure Sensor 34D