Define Switching Limits For The Hysteresis Function; Define Switching Limits For The Window Function; User Settings (Optional); Set Delay For The Switching Outputs - IMI Norgren 34D Series Operation Manual

Electronic pressure sensor
Table of Contents

Advertisement

9.3.2 Define switching limits for the hysteresis function

► [ou1] / [ou2] must be set as [Hno] or [Hnc].
► Select [SP1] / [SP2] and set the value at which the output is set.
► Select [rP1] / [rP2] and set the value at which the output is reset.
rPx is always smaller than SPx. The unit only accepts values which are lower than
the value for SPx.

9.3.3 Define switching limits for the window function

► [ou1] /[ou2] must be set as [Fno] or [Fnc].
► Select [FH1] / [FH2] and set the upper limit value.
► Select [FL1] / [FL2] and set the lower limit value.
FLx is always lower than FHx. The unit only accepts values which are lower than
the value for FHx.

9.4 User settings (optional)

9.4.1 Set delay for the switching outputs

[dS1] / [dS2] = switching delay for OUT1 / OUT2.
[dr1] / [dr2] = reset delay for OUT1 / OUT2.
► Select [dS1], [dS2], [dr1] or [dr2] and set a value between 0 and 50 s (at 0 the
delay time is not active).
For this unit the parameters [dSx] und [drx] for the set and reset points
are designed strictly to the VDMA guideline.

9.4.2 Set output logic for the switching outputs

► Select [P-n] and set [PnP] or [nPn].

9.4.3 Set damping for the switching signal

► Select [dAP], set the value in seconds; setting range 0.000...4.000 s (T value:
63 %). At 0.00 [dAP] is not active.
17
Electronic Pressure Sensor 34D
Operation manual
7503756000000050 05/2019