8.2 Explanation of the menu

8.2.1 Explanation of the menu level 1

SPx/rPx
FHx/FLx
EF
8.2.2 Explanation of the menu level 2
rES
ou1
ou2
dS1 / dS2
dr1 / dr2
uni
P-n
Lo
Hi
dAP
coLr
cFL / cFH
diS
12
Upper / lower limit value for system pressure at which OUT1
switches with hysteresis setting. SP1/rP1 is displayed if the
parameter [Hno] or [Hnc] for OUT1 was set in the extended
functions "EF" menu.
Upper / lower limit value for system pressure at which OUT1
switches with window setting. FH1/FL1 appears when the
parameter [Fno] or [Fnc] was set for OUT1 in the menu
Extended Functions "EF".
Extended functions / opening of menu level 2.
Restore factory setting.
Output function for OUT1:
• Switching signal for the pressure limit values: hysteresis
function [H ..] or window function [F ..], either normally open [.
no] or normally closed [. nc].
Output function for OUT2:
Analogue signal for the current system pressure: 4...20 mA [I] or
0...10 V [U]
Switch-on delay for OUT1.
Switch-off delay for OUT1
Standard unit of measurement for system pressure (display):
[bAr] / [mbar] / [MPA] / [kPA] / [PSI] / [inHG] .
Output logic: pnp / npn.
Minimum value memory for system pressure.
Maximum value memory for system pressure.
Damping of the measured signal.
Assignment of the display colours "red" and "green" within the
measuring range.
Lower / upper value for colour change.
Parameter only active after selection of a freely definable colour
window in the coLr parameter: [r-cF] or [G-cF
Update rate and orientation of the display.
Electronic Pressure Sensor 34D
Operation manual
7503756000000050 05/2019