9.2 Configure display (optional)

► Select [Uni] and set the unit of measurement:
[bAr], [mbAr],
[MPA], [kPA],
[PSI],
[inHG]
The selectable units of measurement depend on the respec-tive unit.
► Select [diS] and set the update rate and orientation of the display:
[d1]: update of the measured values every 50 ms.
[d2]: update of the measured values every 200 ms.
[d3]: update of the measured values every 600 ms.
[rd1], [rd2], [rd3]: display as for d1, d2, d3; rotated by 180°.
[OFF] = The measured value display is deactivated in the Run mode. The LEDs
remain active even if the display is deactivated.
Error messages are displayed even if the display is deactivated.
Even with unsteady pressure characteristics [d1] provides optimum
readability; the corresponding algorithms are stored.

9.3 Set output signals

9.3.1 Set output functions

► Select [ou1] and set the switching function:
[Hno] = hysteresis function/NO,
[Hnc] = hysteresis function/NC,
[Fno] = window function/NO,
[Fnc] = window function/NC.
► Select [OU2] and set the function:
[I] = current signal 4...20 mA
[U] = voltage signal 0...10 V
16
Electronic Pressure Sensor 34D
Operation manual
7503756000000050 05/2019