Lscccls; Snwlrcls - ABB Relion 630 Series Manual

Load shedding controller iec 61850 point list manual
Hide thumbs Also See for Relion 630 Series:
Table of Contents

Advertisement

1MRS757261 C
3.1.3
3.1.4
PML630
Point List Manual

LSCCCLS

Table 6:
LSCCCLS
Attribute name
DATA type
CCLS class
CCLS
Data
Common Logical node information
Mod
ABB_c_dINC
Beh
ABB_a_dINS
Health
ABB_c_dINS
NamPlt
ABB_b_dLPL
Controls
ManLSCmd
ABB_v4_dSPC

SNWLRCLS

Table 7:
SNWLRCLS
Attribute name
DATA type
RCLS class
RCLS
Data
Common Logical Node Information
Mod
ABB_c_dINC
Beh
ABB_a_dINS
Health
ABB_c_dINS
NamPlt
ABB_b_dLPL
Measured Values
NtwAvbPwr
ABB_v2_dMV
NtwLod
ABB_v2_dMV
NtwPwrBal
ABB_v2_dMV
NtwLodInhM
ABB_v2_dMV
Table continues on next page
Logical node extensions
Explanation
Contingency load shedding (Manual
LS)
Mode (Manual load shed function
Enable / Disable / Test command /
status)
Behaviour (Reflects the mode of the
function)
Health
Name plate
Subnetwork manual load shed
command
Explanation
Contingency load shedding related -
Subnetwork information
Mode
Behaviour
Health
Name plate
Network total available power (Sum of
power values from all generators and
grid transformers inclusive of
maximum capabilities)
Network total load
Network power balance (The spinning
reserve value of the network)
Network load inhibit by Operator (Load
value that is inhibited from being shed
by the operator)
Section 3
M/O/E
M
M
M
M
M
E
M/O/E
M
M
M
M
M
E
E
E
E
13

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion pml630

Table of Contents