Mvggio; Spvnzbat - ABB Relion 630 Series Manual

Load shedding controller iec 61850 point list manual
Hide thumbs Also See for Relion 630 Series:
Table of Contents

Advertisement

Section 3
Logical node extensions
3.2.21
3.2.22
26

MVGGIO

Table 31:
MVGGIO
Attribute
DATA type
GGIO class
GGIO
Data
Common logical node information
Mod
ABB_a_dINC
Beh
ABB_a_dINS
Health
ABB_c_dINS
NamPlt
ABB_a_dLPL
Status
AnIN
ABB_a_dMV

SPVNZBAT

Table 32:
SPVNZBAT
Attribute
DATA type
ZBAT class
ZBAT
Data
Common logical node information
Mod
ABB_a_dINC
Beh
ABB_a_dINS
Health
ABB_c_dINS
NamPlt
ABB_a_dLPL
Status
Vol
ABB_b_dMV
BatHi
ABB_a_dSPS
BatLo
ABB_a_dSPS
OpBatLo
ABB_v1_dSPS
OpBatHi
ABB_v1_dSPS
Explanation
Generic measured value
Mode
Behaviour
Health
Name plate
Measurement Value
Explanation
Station battery supervision
Mode
Behaviour
Health
Name plate
Battery voltage
Battery high (voltage or charge -
overcharge)
Battery low (voltage or charge)
Operate command when battery
voltage drops below lower limit
Operate command when battery
voltage exceeds upper limit
1MRS757261 C
M/O/E
M
M
M
M
O
M/O/E
M
M
M
M
M
O
O
E
E
PML630
Point List Manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion pml630