Ldmmxu; Spggio - ABB Relion 630 Series Manual

Load shedding controller iec 61850 point list manual
Hide thumbs Also See for Relion 630 Series:
Table of Contents

Advertisement

Section 3
Logical node extensions
3.2.17
3.2.18
24
Attribute
DATA type
Beh
ABB_a_dINS
Health
ABB_c_dINS
NamPlt
ABB_b_dLPL
Control
Pos
ABB_b_dDPC

LDMMXU

Table 27:
LDMMXU
Attribute
DATA type
MMXU class
MMXU
Data
Common logical node information
Mod
ABB_c_dINC
Beh
ABB_a_dINS
Health
ABB_c_dINS
NamPlt
ABB_b_dLPL
Measurement
TotW
ABB_c_dMV
LodPrioSt
ABB_v1_dINS
InhLSSt
ABB_v1_dINS

SPGGIO

Table 28:
SPGGIO
Attribute
DATA type
GGIO class
GGIO
Data
Common logical node information
Mod
ABB_a_dINC
Beh
ABB_a_dINS
Health
ABB_c_dINS
NamPlt
ABB_a_dLPL
Status
Ind
ABB_c_dSPS
Explanation
Behaviour
Health
Name plate
Position
Explanation
Load feeder circuit breaker power value
Mode
Behaviour
Health
Name plate
Total active power (Total P)
Feeder priority
Inhibit load for LS status
Explanation
Test mode status of PML630
Mode
Behaviour
Health
Name plate
Test mode status
1MRS757261 C
M/O/E
M
M
M
M
M/O/E
M
M
M
M
O
E
E
M/O/E
M
M
M
M
O
PML630
Point List Manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion pml630