TAbLE oF CoNTENTs SyStem ComponentS ......................................4 overview of DUAL DeCoDer operAtion ..............................5 ™ Decoder Benefits ....................................... 5 SyStem overview ....................................... 6 inStALLAtion of DUAL DeCoDer moDULe ..............................7 Installation for Combined Decoder and ICM-600 Module..........................7 wire SpeCifiCAtionS AnD inStALLAtion ................................ 8 Using Pre-Existing Wire ......................................
CoMpoNENTs DUAL 1 DUAL 2 DUAL S DUAL 48M i r e l i d d i n i e l iD wirE (ExAMpLE) Place ground plate in 6” wide trench, perpendicular to shielding wire, 8 feet away, 36” below ground level.
ovErviEW oF DUAL DECoDEr opErATioN ™ DUAL two-wire decoder technology permits control of irrigation Decoder benefits ™ systems over relatively long distances by attaching waterproof Decoder systems save wire. A significant benefit is the ability decoders as needed in a low voltage, direct burial two-wire to operate up to 48 stations with only two wires, instead of path.
sysTEM ovErviEW i-CorE CoNTroLLEr MAx DisTANCE To END oF TWo-WirE pATh iD1 WirE (14 Ga) 5000 fEET (1500 m) Or iD2 WirE (12 Ga) 7500 fEET (2300 m) DUAL -1 (OnE-STATiOn DEcODEr) groUND pLATE (Or GrOUnD rOD) DBr/y-6 wATErprOOf cOnnEcTOrS in ALL TwO-wirE pATH SpLicES DUAL-s sUrgE ArrEsTor MAxiMUM DiSTAncE 5000 fEET (1500 M)
Slide the module lock to the locked “Power On” position. Hunter I-CORE series controllers and provides two-wire decoder The I-CORE will apply power to the module and recognize it outputs for the Hunter DUAL family of field decoders. for decoder use (controller maximum station size is now 48 stations).
As lightning damage is never covered by warranty, service troubles. Hunter provides two types of wire for use with it is in the installer’s best interest to share what Hunter has I-CORE DUAL decoder systems.
TypiCAL WirE LAyoUT single Two-Wire path Two Two-Wire paths DUAL-s sUrgE SUpprESSiOn NoTE: Do not loop the two-wire path back to the controller.
Page 10
TypiCAL WirE LAyoUT single Two-Wire path With T-splices Decoder Controller iD1: Up TO 5000fT/ 1500 M frOM cOnTrOLLEr TO EAcH EnD Of wirE pATHS. iD2: Up TO 7,500 fT/2300 M frOM cOnTrOLLEr TO EAcH EnD Of wirE pATHS NoTE: Do not loop the two-wire path back to the controller.
WirE spECiFiCATioN AND iNsTALLATioN Connecting the Two-Wire paths Turn Controller power OFF. NoTE: if decoder(s) have not been installed on the two-wire path(s), the decoder output Route the red and blue wire paths from the field up through module will display “Line open”. the wire openings or conduit into the controller wiring compartment.
Turn controller power ON. two-wire path. Decoders can also be programmed in the field with the Hunter ICD-HP Handheld Programmer, if available. Insert the stripped end of the red wire from a DUAL decoder Program the station number(s) into the decoders, and then write into one of the two Programming Ports to the right of the the station number assignments on the label on the decoders.
Page 13
ovErviEW oF DECoDEr progrAMMiNg The display will briefly show “Reading DONE” when the 11. The display will indicate when programming has been module has completed identification of the decoder. completed by showing “Programming DONE”. If the decoder has been accidentally disconnected or If the decoder red/blue wires are not fully inserted into the malfunctions, the display will show “Programming ERROR”.
Page 14
ovErviEW oF DECoDEr progrAMMiNg NoTE: Decoders may be reprogrammed at any time. if it is necessary to change the station numbers previously programmed into the decoder, the decoder may be reconnected to the programming port. the station number(s) will be displayed. Conduct the programming procedure outlined above to reprogram the decoder.
NoTE: Decoder wire runs and connections temperature changes. hunter recommends at least must be completely waterproof. Decoder 5 feet/1.5 m slack for each decoder to allow it to wiring is more critical than "conventional"...
Page 16
iNsTALLiNg ThE DECoDErs Identify the color-coded wires on the decoder. The red Each pair color-coded decoder output wires operates and blue wires connect to the red and blue wire path from one or two solenoids up to 100 feet/33 m away (greater the controller.
4" x 36" x 0.0625" (100 mm x 2.4 m x 1.58 mm). A 25-foot (8 m) continuous length Hunter DUAL-S surge arrestors must be used on all DUAL (no splices allowed unless using exothermic welding process) of 6 two-wire systems.
LighTNiNg proTECTioN AND groUNDiNg in-Line surge Arrestor installation End of Line surge Arrestor installation Controller power must be OFF when installing surge Controller power must be OFF when installing surge protection on the two-wire path. protection in the two-wire path. Select the location for the DUAL-S surge arrestor.
Page 19
LighTNiNg proTECTioN AND groUNDiNg in-Line Surge Arrestor installation Solid bare copper shielding wire Decoder ground wire Place ground plate in 6" (15 cm) wide trench, perpendicular to shielding wire, 8 feet (2.5 m) away, 36" (1 m) below ground level. Surround plate evenly with PowerSet material.
DiAgNosTiCs The DUAL decoder module has features and diagnostics to Find solenoid Function help you troubleshoot installation issues and check the status of The “Find Solenoid” function allows the users to activate solenoid operation. Basically, two functions are available to the the solenoid of a single station in a mode the produces a user in the Diagnostic mode: “chattering”...
Wireless programmer If one or more station numbers are listed on the display, troubleshoot those stations. If there is no station number, This Hunter product allows wireless connection troubleshoot the two-wire path connections. with DUAL decoders, even when they are wired into field installations.
Page 22
TroUbLEshooTiNg Press the Mode (center) button on the DUAL48M control Observe the current draw with no stations running. Divide panel. Select “Diagnostics” with the arrows, and press the current draw by the number of decoder modules Mode to select. connected to the controller.
Page 23
TroUbLEshooTiNg Line Fault: If the DUAL48M says “Line Fault” when no stations are running, the most likely cause is a direct short between the two wires in the two wire path (red and blue). If the Line Fault message only appears when a station is turned on, the problem is most likely a short in the decoder-to-solenoid wiring for the affected stations.
Page 24
TroUbLEshooTiNg * Current Draw Too Low: In a low current situation, the controller If No Stations Will Activate: will retry the command to the station up to 3 times. Verify that slide lock is in the Power On position and that The DUAL48M display will show the station number when it is power is on to the DUAL48M module (display appears).
Page 25
TroUbLEshooTiNg Clear Fault Alarms: Press the – button on the ICore facepack to clear the Fault message and/or Alarm light. Special Notes: ICore Decoders are not compatible with mechanical relays. When combining DUAL48M with conventional ICore station output modules, not all stations will be available for decoder addressing.