■ CALIBRATION FLOW CHART
LD1*
G
Fine Adjustments ?
LD2
LD3
G
PUSH
1 – 2 s
MODE
LD1
R
FINE ZERO
LD2
CALIBRATION MODE
G
LD3
or
UP
DOWN
PUSH
MODE
LD1
R
FINE SPAN
LD2
CALIBRATION MODE
LD3
or
UP
DOWN
G
PUSH
MODE
LD1*
G
LD2
LD3
POWER ON
I/O Ranging ?
RUN MODE
PRESS & HOLD
Once the transmitter
LD1
enters the fine zero
R
calibration mode,
LD2
the output goes to
R
preadjusted 0%
value regardless
LD3
of the present input
signal.
PUSH
Once the transmitter
LD1
enters the fine span
R
calibration mode,
LD2
the output goes to
preadjusted 100%
value regardless
LD3
of the present input
R
signal.
PUSH
RUN MODE
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: + 81 ( 6 ) 6659-8201 Fax: + 81 ( 6 ) 6659-8510 E-mail: info@m-system.co.jp
MODE
Control
UP
Buttons
DOWN
> 5s
MODE
Apply simulated 0% input signal.
INPUT
CALIBRATION
MODE
Apply simulated 100% input signal.
MODE
Adjust simulated input until the output meter
shows desired 0% output.
OUTPUT
CALIBRATION
MODE
Adjust simulated input until the output meter
shows desired 100% output.
MODE
When you set 0% or 100% input/output ranges,
keep pressing UP or DOWN button until the
LD1 blinks for approx. 2 seconds and turns off,
which indicates the setup is complete.
When you release the button, the LD1 is returned
to ON.
If the LED does not change, the entered level may
be inappropriate: e.g. out of usable range.
*For the model M3LR-x/A, the green LED is blinking.
For the model M3LR-x/B, the green LED turns on.
Amber LED
A
G
Green LED
R
Red LED
0% INPUT
PUSH
DOWN
CONFIGURED
100% INPUT
PUSH
UP
CONFIGURED
0% OUTPUT
PUSH
DOWN
CONFIGURED
100% OUTPUT
PUSH
UP
CONFIGURED
EM-2662-A P. 6 / 7