 Calibrate of Output
Measurement equipment will be needed for calibrate output such as multi
meter etc.
In order to calibrate output, Click
to calibration mode then choose
 Calibrate Zero turns on the minimum power. Minimum input will
show on display and reading output by multi meter then setup by
click
save and go to the next step
 Calibrate Span turns on the maximum power. Display will show the
maximum input and multi meter will show maximum output then
adjust by click
save and go to the next step
P.S. Display panel show only value of input. In order to display analog
output, multi meter would be needed.
Wisnu and Supak Co., Ltd 102/111-112 Tessabansongkroh Rd., Ladyao, Jatujak, Bangkok 10900
Tel (662)591-1916, (662)954-3280-1, Fax (662)580-4427, www.wisco.co.th, E-mail
Output
Zero
until get desire value for output an then click Exit for
until got desired output then click Exit for
WISCO DP70 Manual V2.0
Span
Exit
button and hold for 3 second to login
and click
to select revise function
Edit: 08/04/2020
Page 13 of 13