Mode Thermocouple R (Ohm) Voltage Current Menu Input Type is for setting type of input. DP70 has 6 type of input which is Thermocouple, RTD, R (Ohm), mV, Voltage and Current as detail below Thermocouple Input Thermocouple Type R...
Function of each button in Hi Value mode: to increase Mode to decrease changing position WISCO DP70 Manual V2.0 Page 7 of 13 Wisnu and Supak Co., Ltd 102/111-112 Tessabansongkroh Rd., Ladyao, Jatujak, Bangkok 10900 Tel (662)591-1916, (662)954-3280-1, Fax (662)580-4427, www.wisco.co.th, E-mail info@wisco.co.th...
Page 13
Mode Decrease value changing position Example DP70 Input Type is RTD (PT100) set up Input range as 0-200. Hi = 200 and Low = 0 Input = 0 °C Output = 4 mA Input = 200 °C Output = 20 mA WISCO DP70 Manual V2.0...
Page 15
Alarm 2 is on when value is lower than 30 and alarm 2 is off when value is (30+1) = 31 WISCO DP70 Manual V2.0 Page 11 of 13 Wisnu and Supak Co., Ltd 102/111-112 Tessabansongkroh Rd., Ladyao, Jatujak, Bangkok 10900 Tel (662)591-1916, (662)954-3280-1, Fax (662)580-4427, www.wisco.co.th, E-mail...
Page 17
P.S. Display panel show only value of input. In order to display analog output, multi meter would be needed. Edit: 08/04/2020 WISCO DP70 Manual V2.0 Page 13 of 13 Wisnu and Supak Co., Ltd 102/111-112 Tessabansongkroh Rd., Ladyao, Jatujak, Bangkok 10900 Tel (662)591-1916, (662)954-3280-1, Fax (662)580-4427, www.wisco.co.th, E-mail...