4286/4500 Voice Module Set up and Troubleshooting
In this document we will discuss the following:
1.
Pre-Installation Notes
2.
The Wiring
3.
System Programming
st
4.
4286 1
Time Accessing and Programming
5.
4500 Integration
6.
4500 Troubleshooting
7.
4286 Troubleshooting
8.
Voice Descriptor Word List
Pre-Installation Notes:
1. VOIP phone service is not supported.
2. DSL requires an RJ31X DSL filter.
Wiring Notes:
1. When using a power supply you MUST share a common ground with the control panel.
2. The 4286 wires up directly to the keypad Terminals on your Control panel.
3. Observe the panels ECP (keypad data) wire runs and do not exceed the 2000' max distance the panel offers
(1500' on vista20 and lower control panels).
4. Existing wires connected to the "Handset" terminals on control must be moved from there to terminals 3
and 4 on the 4286.
5. Place a 2 conductor wire between terminals 21 and 22 to terminals 1 and 2 on the 4286.
Back to Top
Figure 1: Vista-10/15/20p Wiring
- 1 -
Tech Support
Updated 7/27/10

Advertisement

loading

Summary of Contents for Honeywell 4286

  • Page 1 4. Existing wires connected to the “Handset” terminals on control must be moved from there to terminals 3 and 4 on the 4286. 5. Place a 2 conductor wire between terminals 21 and 22 to terminals 1 and 2 on the 4286. Figure 1: Vista-10/15/20p Wiring...
  • Page 2: System Programming

    Figure 2: Vista-40/50/128b/bp & 250bp Figure 3: Vista-32fb & 128fb/fbp & 250fbp System Programming: Notes: 1. The 4286 has a Non-Changeable address of 04 and can not be changed. See below for programming on various panels: Back to Top Tech Support...
  • Page 3 Step-by-Step Programming the Vista 10/15/20p: 1. There is no device programming on these panels. In order to program the panel to recognize the 4286 you simply add the “Voice Module Access Code” Access Code for Phone Module [00] 00 = disable...
  • Page 4 4286 1 time accessing and programming: 1. To Access the 4286 programming, pick up any phone that is tied to terminals 3 & 4 on the 4286 and enter your 2 digit phone code. The system will give you the status of the Control Panel.
  • Page 5 Step-by-Step Control Panel Type Enter 1 for the Vista-10, 10se-Via30p,30pse – 4140xmp Enter 2 for the Vista-10/15/20p, Vista-20, 20HW, 20SE, 20HWSE & Vista- Enter 4 for the Vista-40, 50p, 128b/bp, 250bp and 128fb/fbp and 250fbp For Integration of the 4500 Thermostat module complete the following: Units of Temperature 1 –...
  • Page 6 Step-by-Step 000 – No Announcement (See Below for word list) Word Word Word Word Index Index Index Index Word Word Word Word DOWNSTAIRS MEDICAL STORAGE ALARM DRIVEWAY MOTHERS DUCT MOTION SYSTEM* APARTMENT APPLIANCE EAST TEMPERATURE AREA EQUIPMENT NORTH TOOL ATTIC EXIT BABY FACTORY...
  • Page 7 HVAC contractor be contacted for information on the type of heating system and the amount of "span" (i.e. temperature swing) that should be set with the 4286 phone module. 5. For more wiring notes see the installation instructions.
  • Page 8 Step-by-Step Figure 11: Addressing the 4500 Basic operations are: 1. 4500 is used to operate the HVAC system with the alarm panel is armed in the AWAY or MAXIMUM mode. Premises Thermostat should be set above (in heat mode) or below (in cool mode) the 4500 Set-back setting.
  • Page 9: Menu Selections

    Setting the 4500 Thermostat: To enter and use the 4286 thermostat programming mode: 1. There must be at least one thermostat programmed into the system by way of the 4286 installer programming mode entry. 2. Obtain phone access from the phone module. Enter the 2-digit phone code. Enter the 4-digit system code if prompted.
  • Page 10 4286 programming mode. See figure 11 above 2. Check the connections from the 4286 to the 4500, and make sure that the cable connecting the 4500s to the 4286 faces the correct direction (yellow toward the corner of the 4286 board).
  • Page 11 Check the wiring of the 4286 on the ECP terminals of the panel. Make sure the harness is plugged into the proper plug on the 4286, and not the plug intended for the 4500, make sure it is plugged in with yellow towards the center of the board.